0 troubleshooting, 0 troubleshooting table, 0 troubleshooting 11.0 troubleshooting table – ARI Armaturen DP34 EN User Manual

Page 27

Advertising
background image

0040504000 1210

Page 27

Operating and installation instructions

Pneumatic actuators - DP32 / DP33 / DP34

10.0 Troubleshooting

In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.

If malfunctions cannot be eliminate with the help of the following table „11.0
Troubleshooting table
“, the supplier or manufacturer should be consulted.

11.0 Troubleshooting table

ATTENTION !
It is essential that the safety regulations are observed when identifying faults.

ATTENTION !
- read point 7.0 and 8.0 prior to
dismantling and repair work !
- read point 6.0 before restarting the plant !

Fault

Possible causes

Corrective measures

Actuator unit does not move No compressed air on the

control pressure line

Discern the causes and remedy

Actuator unit has been
improperly installed

Check the actuator’s operating
mode and connect to the
control pressure line in
accordance to this operating
mode.

The rolling diaphragm is defect

Replace the rolling diaphragm
and springs

Manual emergency adjustment
is blocked

Set the manual emergency
adjustment into the correct
position (both position
indicators must be at the
starting point and be in the
same position).

There is not enough
positioning force available

Wrong spring pieces
(the spring range

of the

actuator is wrong)

Replace springs (actuator unit)

Stem sealing has a leak

Renew the stem sealing

The ventilation is plugged and
the air cannot escape from the
actuator unit

Screw cap must be disengaged

The actuator unit does not
ventilate sufficiently

Check the control adjustment