0 troubleshooting table, Operating and installation instructions preso – ARI Armaturen PRESO EN User Manual

Page 11

Advertising
background image

Rev. 0040402000 0410

Page 11

Operating and installation instructions

PRESO

®

9.0 Troubleshooting table

ATTENTION !
- read point 10.0 and 11.0 prior
to dismantling and repair work!
- read point 6.0 before restarting the plant !

Fault

Possible cause

Corrective measures

No flow

Flange covers not removed

Remove flange covers

Little flow

Dirt sieve clogged

Clean / replace sieve

Piping system clogged

Check piping system

Pressure regulating valve
does not respond, no flow

Pressure range too high

Reset (point 6.0) or replace the
pressure regulating valve

Stainless steel bellow defective

Replace pressure regulating valve

Medium viscous or sticky

Use heating jacket

The valves and piping must be
protected against freezing and
solidifying media

Use heating jacket !

Valve installed against flow direction

Turn the valve into flow direction

Pressure regulating valve
seat leaking

Pressure regulating valve flattering

Refer to separate point “Flattering”

Medium contaminated; foreign body
between seat and disc

Replace

pressure regulating valve

Flange broken

Damage during transport

Replace

pressure regulating valve

Flange bolts not evenly tightened

Replace

pressure regulating valve

Transfer of unacceptable forces, e.g.
bending or torsional forces

Install free of tension

Pressure regulating valve
constantly open

Spring corroded by medium and broken Replace pressure regulating valve

Spindle guide corroded

Flattering

Pressure regulating valve capacity too
high

Install smaller pressure regulating
valve

Capacity too low

Pressure regulating valve not applied
unsuitable for plant conditions

Select and install suitable pressure
regulating valve

Advertising