AMETEK 7100 Leak Detect Stik User Manual

Page 6

Advertising
background image

4

The type of information contained in each reading varies depending on the probe type. Table 2 specifies the data

pattern for various probe types.

Table 2 - Reading Data Type Specification by Probe Type

Types 1, 2, 3

Types 4, 5, 6

Reading 1

Temp 1

Temp 1

Reading 2

Product or Water*

Product or Water*

Reading 3

Low Ref Temp

Temp 2

Reading 4

Product

Product

Reading 5

High Ref Temp

Temp 3

Reading 6

Product

Product

Reading 7

Low Ref Temp

Temp 4

Reading 8

Product

Product

Reading 9

High Ref Temp

Temp 5

Reading 10

Product

Product

Reading 11

Circuit Temp

Circuit Temp

Reading 12

Product

Product

Reading 13

Low Ref Temp

Low Ref Temp

Reading 14

Product

Product

Reading 15

High Ref Temp

High Ref Temp

* For single float probes, this frame contains product data.

For dual float probes, this frame contains water data.

When calculating Water or Product positions, one must consider whether or not the probe uses a reference

magnet. For probes that use a reference magnet (type 3 and type 6), position can be calculated using the

following formula:

Position = Measured Period/Wire Speed

Where:

Measured Period = the time between pulses in a reading (ms)

Wire Speed = (ms / inch)

Position = distance from internal reference

For probes that do not use a reference magnet (types 1, 2, 4, and 5), position can be calculated using the

following formula:

Position = Measured Period/Wire Speed*2