Installation, Agency listings and approvals, Product line information – Notifier FST-851 User Manual

Page 2

Advertising
background image

Page 2 of 2 — DN-6936:B • 12/07/2011

Notifier® and FlashScan® are registered trademarks of Honeywell

International Inc.

©2011 by Honeywell International Inc. All rights reserved. Unauthorized use

of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.

www.notifier.com

Made in the U.S. A.

Installation

The FST Series plug-in intelligent thermal detectors use a sep-

arate base to simplify installation, service, and maintenance.

Installation instructions are shipped with each detector. A spe-

cial tool allows maintenance personnel to plug in and remove

detectors without using a ladder
Mount base (all base types) on an electrical backbox which is

at least 1.5" (3.81 cm) deep. For a chart of compatible junction

boxes, see DN-60054.

NOTE: 1) Because of the inherent supervision provided by the
SLC loop, end-of-line resistors are not required. Wiring “T-taps” or
branches are permitted for Style 4 (Class “B”) wiring. 2) When
using relay or sounder bases, consult the ISO-X(A) installation
sheet I56-1380 for device limitations between isolator modules
and isolator bases.

Agency Listings and Approvals

These listings and approvals apply to the modules specified in

this document.In some cases, certain modules or applications

may not be listed by certain approval agencies, or listing may

be in process. Consult factory for latest listing status.

UL Listed: S747.

ULC Listed: S6978.

MEA Listed: 383-02-E.

• FM Approved.

CSFM: 7270-0028:0196.

BSMI: CI313066760025.

CCCF: Certif. # 2004081801000018.

U.S. Coast Guard: 161.002/42/1 (NFS-640); 161.002/50/0

(NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)).

Lloyd’s Register: 11/600013 (NFS2-640/NFS-320/NFS-

320C, excluding B210LP(A)).

Product Line Information

NOTE: “A” suffix indicates ULC Listed model.

FST-851: Intelligent thermal detector. Must be mounted to one

of the bases listed below.
FST-851A: Same as FST-851 but with ULC Listing.
FST-851R: Intelligent thermal detector with rate-of-rise fea-

ture.
FST-851RA: Same as FST-851R but with ULC Listing.
FST-851H: Intelligent high-temperature thermal detector.
FST-851HA: Same as FST-851H but with ULC Listing.

INTELLIGENT BASES

NOTE: “A” suffix indicates ULC Listed model.

NOTE: For details about intelligent bases and their mounting, see
DN-60054.

B210LP(A): Standard U.S. flanged low-profile mounting base.
B210LPBP: Bulk pack of B210LP; package contains 10.

B501(A):

Standard European f

langeless mounting base.

B501BP: Bulk pack of B501; package contains 10.
B200S

(A)

: Addressable Intelligent, programmable sounder

base capable of producing sound output in high or low volume

with ANSI Temporal 3, ANSI Temporal 4, continuous tone,

marching tone, and custom tone.
B200SR

(A)

: Intelligent sounder base capable of producing

sound output with ANSI Temporal 3 or continuous tone.

Replaces B501BH series bases in retrofit applications.
B224RB

(A)

: Intelligent relay base. Screw terminals: up to 14

AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0 A @ 30 VDC

resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC induc-

tive.
B224BI

(A)

: Intelligent isolator base. Isolates SLC from loop

shorts. Maximum: 25 devices between isolator bases; see

Note 2 under Installation.

ACCESSORIES

F110: Retrofit flange to convert B210LP(A) to match the

B710LP(A) profile, or to convert older high-profile bases to

low-profile.
F110BP: Bulk pack of F110; package contains 15.
F210: Replacement flange for B210LP(A) base.
RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Fits U.S.

single-gang electrical box. Supported by B210LP(A) and

B501(A) bases only.
SMB600: Surface mounting kit, flanged.
M02-04-00: Test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows installation and/or

removal of FlashScan® Series detector heads from base in

high ceiling installations. Includes T55-127-010.
T55-127-010: Detector removal tool without pole.
XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524

m) sections.