Page 2 of 4 — DN-6999:C • 10/06/2010

NMM-100P(A) Mini Monitor Module

• Built-in type identification automatically identifies this device

as a monitor module to the panel.

• Powered directly by two-wire SLC loop. No additional power

required.

• High noise (EMF/RFI) immunity.
• Tinned, stripped leads for ease of wiring.
• Direct Decade entry of address: 01 – 99 on FireWarden-

100-2, 01 – 50 on FireWarden-50.

The NMM-100P(A) Mini Monitor Module can be installed in a

single-gang junction directly behind the monitored unit. Its

small size and light weight allow it to be installed without rigid

mounting. The NMM-100P(A) is intended for use in intelligent,

two-wire systems where the individual address of each module

is selected using rotary switches. It provides a two-wire initiat-

ing device circuit for normally-open-contact fire alarm and

security devices. NMM-100P(A)

NMM-100P(A) APPLICATIONS

Use to monitor a single device or a zone of four-wire smoke

detectors, manual fire alarm pull stations, waterflow devices, or

other normally-open dry-contact devices. May also be used to

monitor normally-open supervisory devices with special super-

visory indication at the control panel. Monitored circuit/device

is wired as an NFPA Style B (Class B) Initiating Device Circuit.

A 47K ohm End-of-Line Resistor (provided) terminates the cir-

cuit.

NMM-100P(A) OPERATION

Each NMM-100P(A) uses one of the available module

addresses on an SLC loop. It responds to regular polls from

the control panel and reports its type and the status (open/nor-

mal/short) of its Initiating Device Circuit (IDC).

NMM-100P(A) SPECIFICATIONS

Nominal operating voltage: 15 to 32 VDC.
Average operating current: 350 μA, 1 communication every

5 seconds, 47k EOL; 600 μA Max. (Communicating, IDC

Shorted).
Maximum IDC wiring resistance: 40 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 400 μA.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.

Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x

0.65" (1.651 cm) deep.
Wire length: 6" (15.24 cm) minimum.

NZM-100(A) Interface Module

• Supports compatible two-wire smoke detectors.
• Supervises IDC wiring and connection of external power

source.

• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct Decade entry of address:, 01 – 99 on FireWarden-

100-2, 01 – 50 on FireWarden-50.

• LED flashes during normal operation.
• LED latches steady to indicate alarm on command from

control panel.

The NZM-100(A) Interface Module is intended for use in intelli-

gent, addressable systems, where the individual address of

each module is selected using built-in rotary switches. This

module allows intelligent panels to interface and monitor two-

wire conventional smoke detectors. It transmits the status (nor-

mal, open, or alarm) of one full zone of conventional detectors

back to the control panel. All two-wire detectors being moni-

tored must be UL compatible with the module.

NZM-100(A) APPLICATIONS

Use the NZM-100(A) to monitor a zone of two-wire smoke

detectors. The monitored circuit may be wired as an NFPA

Style B (Class B) or Style D (Class A) Initiating Device Circuit.

A 3.9 K ohm End-of-Line Resistor (provided) terminates the

end of the Style B or D (class B or A) circuit (maximum IDC

loop resistance is 25 ohms). Install ELR across terminals 8

and 9 for Style D application.

NZM-100(A) OPERATION

Each NZM-100(A) uses one of the available module

addresses on an SLC loop. It responds to regular polls from

the control panel and reports its type and the status (open/nor-

mal/short) of its Initiating Device Circuit (IDC). A flashing LED

indicates that the module is in communication with the control

panel. The LED latches steady on alarm (subject to current

limitations on the loop).

NZM-100(A) SPECIFICATIONS

Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum IDC wiring resistance: 25 ohms.
Average operating current: 300 μA, 1 communication and 1

LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K ohms.
External supply voltage (between Terminals T3 and T4):

DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms

maximum. Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x

1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x

2.125" (5.398 cm) deep box.