Architectural/Engineering
Specifications

GENERAL

SpectrAlert Advance speaker and speaker strobes shall mount to a

4” x 4” x 2-1/8” backbox. A universal mounting plate shall be used for

mounting ceiling and wall products. The notification appliance circuit and

amplifier wiring shall terminate at the universal mounting plate. Also,

SpectrAlert Advance speaker strobes, when used with the Sync Circuit.

Module accessory, shall be powered from a non-coded notification appli-

ance circuit output and shall operate on a nominal 12 or 24volts. When

used with the Sync.Circuit Module, 12 volt rated notification appliance cir-

cuit outputs shall operate between nine and 17.5 volts; 24 volt rated notifi-

cation appliance circuit outputs shall operate between 17 and 33 volts.

Indoor SpectrAlert Advance products shall operate between 32°F and

120°F from a regulated DC, or full-wave rectified, unfiltered power supply.

Speaker strobes shall have field-selectable candela settings including 15,

15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185.

SPEAKER

The speaker shall be a System Sensor SpectrAlert Advance model

_______ dual-voltage transformer speaker capable of operating at 25.0 or

70.7 nominal Vrms. It should be listed to UL/ULC 1480 and shall be

approved for fire protective service. The speaker shall have a frequency

range of 400 to 4000Hz and shall have an operating temperature between

32°F and 120°F. Speaker shall have power taps and voltage that are

selected by rotary switches.

SPEAKER STROBE COMBINATION

The speaker strobe shall be a System Sensor SpectrAlert Advance model

__________ listed to UL1480 and UL/ULC 1971 and be approved for fire

protective signaling systems. Speaker shall be capable of operating at

25.0 or 70.7 nominal Vrms selected via rotary switch, and shall have a fre-

quency range of 400 to 4000Hz. Speaker shall have power taps which are

selected by rotary switch. The strobe shall comply with the NFPA 72

requirements for visible signaling appliances, flashing at 1Hz over the

strobe’s entire operating voltage range. The strobe light shall consist of a

xenon flash tube and associated lens/reflector system.

SYNCHRONIZATION MODULE

The module shall be a System Sensor Sync Circuit model MDL listed to

UL/ULC 464 and shall be approved for fire protective service. The module

shall synchronize SpectrAlert strobes at 1Hz. The module shall mount to a

4-11/16” x 4-11/16” x 2-1/8” backbox. The module shall also control two

Style Y (class B) circuits or one Style Z (class A) circuit. The module shall

synchronize multiple zones. Daisy chaining two or more synchronization

modules together will synchronize all the zones they control. The module

shall not operate on a coded power supply.

Ordering Information

NOTE: (W) indicates white coloring; (R), red.
NOTE: “A” suffix indicates ULC-Listed model.

WALL MOUNT

SP(W)(R)(A): Speaker only.
SP(W)(R)V(A): Speaker only, high dB; white.
SPS(W)(R)(A)*: Speaker strobe, selectable candela (15, 15/75,

30, 75, 95, 110, 115).
SPS(W)(R)H(A)*: Speaker strobe, selectable candela, high cd

(135, 150, 177, 185).
SPS(W)(R)V(A)*: Speaker strobe, selectable candela, high dB.

CEILING MOUNT

SPC(W)(R)(A): Speaker only.
SPC(W)(R)V(A): Speaker only, high dB.
SPSC(W*)(R)(A): Speaker strobe, selectable candela (15, 15/

75, 30, 50, 75, 95, 110, 115)
SPSC(W*)(R)H(A): Speaker strobe, selectable candela, high

cd (135, 150, 177, 185)
SPSC(W*)(R)V(A): Speaker strobe, selectable candela, high

dB (15, 15/75, 30, 50, 75, 95, 110, 115).
SPSC(W*)(R)VH(A): Speaker strobe, selectable candela, high

dB, high cd (135, 150, 177, 185).

ACCESSORIES

RFP(A): Retrofit plate (5 pack), red.
RFPW(A): Retrofit plate (5 pack), white.
SPBBSC(A): Ceiling mount backbox skirt, red.
SPBBSCW(A): Ceiling mount backbox skirt, white.
SPBBS(A): Wall mount backbox skirt, red.
SPBBSW(A): Wall mount backbox skirt, white.
TR(A): Wall mount trim ring, red, package of 5.
TRW(A): Wall mount trim ring, white, package of 5.
TRC(A): Ceiling mount trim ring, red, package of 5.
TRCW(A): Ceiling mount trim ring, white, package of 5.
MWBB(A): Wall mount, metal weatherproof backbox
MWBBW(A): Wall mount, metal weatherproof backbox, white
MWBBC(A): Ceiling mount, metal weatherproof backbox
MWBBCW(A): Ceiling mount, metal weatherproof backbox,

white
*NOTE: Add -P to model number for plain housing (no ‘FIRE’
marking on the cover), e.g. SPSW-P

UL Maximum Strobe Current Draw (mA RMS)

Candela

8 to 17.5 Volts

16 to 33 Volts

DC

FWR

DC

FWR

Standard

Candela

Range

15

123

128

66

71

15/75

142

148

77

81

30

NA

NA

94

96

75

NA

NA

158

153

95

NA

NA

181

176

110

NA

NA

202

195

115

NA

NA

210

205

High

Candela

Range

135

NA

NA

228

207

150

NA

NA

246

220

177

NA

NA

281

251

185

NA

NA

286

258

Sound Output

UL Reverberant (dBA @ 10ft)

2W

1W

½W

¼W

Wall Mount SP Series

86

83

80

77

Wall Mount SPV Series

90

87

84

81

Ceiling Mount SPC Series

86

83

80

77

Ceiling Mount SPCV Series

90

87

84

81

Wall Mount SPS Series

85

82

79

76

Wall Mount SPSV Series

89

86

83

80

Ceiling Mount SPSC Series

85

82

79

76

Ceiling Mount SPSCV Series

89

86

83

80

Advertising