ANN-BUS DEVICE ADDRESSING

Each ANN-BUS device requires a unique address (ID Number)

in order to communicate with the FACP. A maximum of 8 devices

can be connected to the FACP ANN-BUS communication circuit.

See the FACP manual for more information.

WIRE REQUIREMENTS: COMMUNICATIONS CIRCUIT

The N-ANN-80 connects to the FACP ANN-BUS communica-

tions circuit. To determine the type of wire and the maximum wir-

ing distance that can be used with FACP ANN-BUS accessory

modules, it is necessary to calculate the total worst case current

draw for all modules on a single 4-conductor bus. The total worst

case current draw is calculated by adding the individual worst

case currents for each module.
NOTE: For total worst case current draw on a single ANN-BUS
refer to appropriate FACP manual.

After calculating the total worst case current draw, the following

table specifies the maximum distance the modules can be

located from the FACP on a single wire run. The table ensures

6.0 volts of line drop maximum. In general, the wire length is lim-

ited by resistance, but for heavier wire gauges, capacitance is

the limiting factor.
These cases are marked in the chart with an asterisk (*). Maxi-

mum length can never be more than 6,000 feet (1,800 m),

regardless of gauge used. See table below.

WIRE REQUIREMENTS: POWER CIRCUIT

• 14 to 18 AWG (0.75 - 2.08 mm

2

) wire for 24 VDC power cir-

cuit is acceptable.

• All connections are power-limited and supervised.
• A maximum of eight N-ANN-80 modules may be connected

to this circuit.

WIRING CONFIGURATION

The following figure illustrates the wiring between the FACP and

ANN-BUS devices.

FACP Wiring to ANN-BUS Device

ORDERING OPTIONS:

N-ANN-80: Black 80 character LCD Annunciator.
N-ANN-80-W: White, 80 character LCD Annunciator.
ANN-SB80KIT-B: Black surface mount backbox with angled

wedge.
ANN-SB80KIT-W: White surface mount backbox with angled

wedge.

Communication Pair Wiring Distance: FACP to Last ANN-BUS Module

Total Worst Case
Current Draw (amps)

22 Gauge

18 Gauge

16 Gauge

14 Gauge

0.100

1,852 ft.

4,688 ft.

* 6,000 ft.

*6,000 ft.

0.200

926 ft.

2,344 ft.

3,731 ft.

5,906 ft.

0.300

617 ft.

1,563 ft.

2,488 ft.

3,937 ft.

0.400

463 ft.

1,172 ft.

1,866 ft.

2,953 ft.

0.500

370 ft.

938 ft.

1,493 ft.

2,362 ft.

0.600

309 ft.

781 ft.

1,244 ft.

1,969 ft.

0.700

265 ft.

670 ft.

1,066 ft.

1,687 ft.

0.800

231 ft.

586 ft.

933 ft.

1,476 ft.

0.900

206 ft.

521 ft.

829 ft.

1,312 ft.

1.000 (max.)

185 ft.

469 ft.

746 ft.

1,181 ft.

ANN-BUS and power
wiring are supervised
and power-limited.

ANN-BUS Device

NFW-50