Notifier APS2-6R 6.0 User Manual

Aps2-6r, 0 amp auxiliary power supply, General

Advertising
background image

DN-60410:C • 10/22/2009 — Page 1 of 2

APS2-6R

6.0 Amp Auxiliary Power Supply

Power Supplies

DN-60410:C • E-122

ap

s2-

yr

.jpg

General

The APS2-6R is a state-of-the-art, 150 watt, switching auxil-
iary power supply providing 24 VDC of filtered DC power. The
APS2-6R provides three 24 VDC output circuits, rated for 6.0
Amps in alarm and 4.0 Amps continuous. It is used for the
operation of peripheral devices for the Onyx Series control
panels.

NOTE: The APS2-6R can also be used with Legacy panels.
Please refer to the APS2-6R manual for more information.

Features

UL 864 Ninth Edition compliant

Lightweight, compact design

120 or 220/240 VAC (@ 50/60 Hz) versions

Output circuits with overload protection

Built-in “brown-out” circuitry

Diagnostic trouble LED

Plug-in connector for in-cabinet applications and screw ter-
minals for remote device applications

Trouble supervision bus

Shares battery and charger circuit with control panel

Power-limited design, per UL requirements

AC Fail supervision and reporting with field-selectable delay
per UL 864

Heavy-duty clamp-type terminals accept up to 12 AWG
(3.1 mm²) wire

Battery voltage supervision

Low battery disconnect

Mounts in a standard CAB-3/CAB-4 Series cabinet.

Construction and Operation

When used with the CAB-3 or CAB-4 Series (CAB-A3/-A4, -
B3/-B4, -C3/-C4, or -D3/-D4), the APS2-6R mounts to a
CHS-4 or CHS-4L mounting chassis. If more than one APS2-
6R is necessary to satisfy Audible/Visual (DC) power require-
ments, connect additional APS2-6R power supplies together
as described in the Installation Instruction Manual #53232.

Specifications

ELECTRICAL SPECIFICATIONS

AC primary input power (TB1): APS2-6R: 120 VAC, 50/60
Hz, 2.9 A., APS2-6RE : 220-240 VAC, 50/60 Hz, 1.5 A.

DC secondary input power (TB3): TB3-1 (+), TB3-2 (–).

24 VDC output power (TB2): Total 6.0 A (4.0 A continuous).
Circuit 1 (TB2-1, TB2-2): 3.0 A @ 24 VDC power-limited. Cir-
cuit 2 (TB2-3, TB2-4):
3.0 A @ 24 VDC power-limited.

24 VDC output power (J9): 6.0 A (4.0 A continuous), Non-
Power Limted.

Relay Contacts (TB4): AC Fail supervision over the SLC.

Fuse: (F2 battery supervision): 32 VAC, 10.0 A, Fast-Acting
Automotive Minifuse.

Trouble supervision bus: J3 output: Form-A contact (open
collector). J4 input: Form-A contact (open collector).

NOTE: J3 and J4 can be interchanged.

Loss of AC indication: Immediate indication (default); 1-2
hour delay (cut JP2); 2-3 hour delay (cut JP2 and JP3).

MECHANICAL SPECIFICATIONS

The APS2-6R measures approximately 8.625" (21.91 cm) x
6.625" (16.83 cm) x 2.375” (6.03 cm) and weighs approxi-
mately 2 lbs (0.91kg).

Cabinet for Mounting

CAB-3/CAB-4 Series: Use CHS-4 and CHS-4L chassis, for
NFS2-3030, NFS2-640, AM2020, AFP1010, NFS-3030, NFS-
640, AFP-400, AFP-300, and System 5000, control panels.

Product Line Information

APS2-6R: 24-volt, filtered power supply (120 VAC input).

APS2-6RE: 24-volt, filtered power supply (220-240 VAC input)

EOLR-1: 12/24 VDC end-of-line relay.

CHS-4: Four-module chassis.

CHS-4L: Four-module chassis (low-profile).

R-47K: End of Line Resistor Assembly

Installation Standards and Codes

This power supply complies with the standards set forth by the
following regulatory agencies:

NFPA Standards

NFPA 72 National Fire Alarm Code

Underwriters Laboratories:

UL 864 Standard for Control Units and Accessories for Fire
Alarm Systems

In addition, the installer should be familiar with the following
standards:

NEC Article 300 Wiring Methods

Applicable Local and State Building Codes

Requirements of the Local Authority Having Jurisdiction