• Ethernet network connection (ITE-listed router/gateway).
• Although not required to meet NFPA, a small UPS is recom-

mended to provide backup power for customer-provided

router/switch (the HP3-300ULX can provide 12 VDC

backup power for small 12 volt routers drawing 500 mA or

less for over 24 hours).

• Dynamic or static IP address (dynamic addressing requires

DHCP server present on the local network. NOTE: DSL and

cable modems typically use dynamic addressing as sup-

plied by network providers).

• UDP port for IP communication with the monitoring station

(default port: 80 may be changed by central station).

• Destination IP addresses of the IP receivers where the

communicator will be sending alarms and other events (If

installed on a private Intranet, the gateway address of the

public router will be required to allow the IP card to access

the Internet and the public router at the central station).

• Panel account ID number (CID).
• Installer password (provided by the monitoring station man-

aging the IP receiver).

• Separate username and password supplied by central sta-

tion for upload/download operation. (Note: this is different

than installation password.)

MOUNTING METHODS

There are four mounting methods depending on project

requirements and panel used.

1. The IP Communicator can be mounted directly inside the

common enclosure used with the NFW-50, NFW2-100,

SFP-5UD, and SFP-10UD. When mounting inside the com-

mon enclosure the IPBRKT is used as shown on the previ-

ous page. A special polycarbonate cover is supplied that

serves to protect the unit from installed batteries.

2. The IP Communicator can be mounted in a CAB-3/4

Series Cabinet using the IP Communicator Chassis Mount-

ing Kit P/N IPCHSKIT. The IPCHSKIT mounts onto a CHS-

4/N, CHS-4L, CHS-M3, or NFS2-640 Chassis. If the sys-

tem configuration does not support the installation of the

IPCHSKIT, use the IPENC enclosure.
3. The IP Communicator can be mounted inside the small

add-on IPENC enclosure. This is typically used with previ-

ous panels that did not use the common enclosure. This will

be connected to the fire alarm panel with a short piece of

conduit.

NOTE: The 411UD application for monitoring Alarm, Trouble and
Supervisory relays of a competitive FACP requires mounting both
the 411UD and IPDACT-2UD inside the HP300ULX.

4. When more power is required, the IP Communicator can

be mounted inside the HP300ULX power supply. The power

supply should be connected to the fire alarm panel with a

short piece of conduit.

NOTE: Refer to the IP Communicator Series Installation Docu-
ment PN 53109 for additional installation information.

PROGRAMMING OPTIONS

1. Console terminal using the HyperTerminal software pro-

gram found on all Microsoft operating systems. Requires

serial programming cable PN ALMSC-119.
2. Local or remote Telnet session via Ethernet connection.

Requires either switch/hub connection or Ethernet cross-

over cable from laptop to Ethernet Port and programming

PC. The PC’s IP address must be set to the default range of

the IPDACT-2/2UD such as 192.168.0.XX.
3. Windows-based configuration software (shipped with IP

Communicator version 6.0 or higher). Version 6.0 permits

use of either Ethernet Crossover cable or Serial Cable.

To Alarm, Trouble,

Supervisory

Output Relays

on FACP

(2.2KS ELRs at FACP)

Communicator Fault

to monitor module

on FACP SLC Loop

or in-line of

NAC on FACP

Connecting the IPDACT, 411UD and HP300ULX