Diagnostic leds, Specifications — 411ud, Specifications — 411 – Notifier 411 Series User Manual

Page 2: Agency listings and approvals, Product line information

Advertising
background image

Page 2 of 4 — DN-6619:A2 • 4/13/2012

separate telephone lines using standard RJ31X or RJ38X

jacks. Both telephone lines are constantly supervised for

proper operation and integrity. If one phone line goes into fault

while the other is working, a report is sent to the central or

remote station.

Diagnostic LEDs

• Communication Fail (visible with front cover in place).
• DACT Trouble (visible with front cover in place) (411UD).
• Channel Active (visible with front cover in place) (411UD).
• Primary Phone Line Active (411UD).
• Secondary Phone Line Active (411UD).
• Modem Active (411UD).

Specifications — 411UD

Listings and Approvals:
• NFPA 72: Central Station Fire Alarm Systems.
• NFPA 72: Remote Station Fire Alarm Systems.
• UL Standard 1635: Digital Alarm Communicator/Transmit-

ters.

• UL Standard 864: Control Units for Fire Alarm Systems.
FCC Registration: OAAUSA-25431-AL-E. Ringer Equiva-

lence: 0.5 B.
For Canadian Applications: IC Certificate Number: 2132

9028 A. Ringer Equivalence Number (REN): 0.2.
Programming: A digital programming unit with a keypad,

model PRO-411, is available for programming the 411 Series.
Operating Power: The 411UD circuit board operates on fil-

tered 12 VDC. The configuration of Jumper J4 determines

whether 12 VDC power is to be supplied directly to the circuit

board, or 24 VDC power is to be supplied and then internally

regulated down to 12 VDC.
DC Power:
• J4 Jumper REMOVED: Filtered, nonresettable and power-

limited 24 VDC (nominal) power must be supplied at TB1

Terminals 7(+) and 8(–). Current requirements are 100 mA

in standby and 170 mA* while communicating.

• J4 Jumper INSTALLED: Filtered, nonresettable and power-

limited 12 VDC (nominal) power must be supplied at TB1

Terminals 7(+) and 8(–). Current requirements are 100 mA

in standby and 170 mA* while communicating.

*NOTE: A maximum of 300 mA is possible with all channels
active, the 411UD communicating, the PRO-411 connected,
and Lamp Test active.
Channels/Inputs:**
• Programmable Channels 1 through 4.
• Power-limited circuitry.
• Fully supervised.
• Operation: All channels NFPA Style B (Class B). Requires

Normally Open contact to trigger.

• Normal operating voltage: 12 VDC.
• Alarm current: 3.34 mA.
• End-of-line resistor: 2.2K ohms.
• Short-circuit current: 3.8 mA per channel/input.
**NOTE: Channels/inputs do NOT support two-wire smoke
detectors.

Form-C Relay:

• Contact rating: 2.0 amps @ 30 VDC (resistive).

Specifications — 411

FCC Registration: OAAUSA-25431-AL-E. Ringer Equiva-

lence: 0.5 B.
For Canadian Applications: IC Certificate Number: 2132

9028 A. Ringer Equivalence Number (REN): 0.2.
Programming: A digital programming unit with a keypad,

model PRO-411, is available for programming the 411 Series.
Operating Power: The 411 may be powered from UL-listed

control panels that output nonresettable and power-limited 12

or 24 VDC power. The configuration of Jumper J4 determines

whether 12 VDC power is to be supplied directly to the 411 cir-

cuit board, or 24 VDC power is to be supplied and then inter-

nally regulated down to 12 VDC.
DC Power: TB1 Terminals 1(+) and 2(–); Terminal 3 is Earth

Ground.
• J4 Jumper removed: Filtered, nonresettable, and power-lim-

ited 24 VDC (nominal) power must be supplied at TB1 Ter-

minals 1(+) and 2(–). Operating voltage provided must be

within 21.3 to 24.0 VDC (UL tested range: –15%, +10%).

Current requirements are 78 mA in standby and 126 mA

while communicating.

• J4 Jumper installed: Filtered, nonresettable, and power-lim-

ited 12 VDC (nominal) power must be supplied at TB1 Ter-

minals 1(+) and 2(–). Operating voltage must be within 11.2

to 12.4 VDC (UL tested range: –15%, +10%). Current

requirements are 78 mA in standby and 126 mA

while

communicating.

NOTE: A maximum of 240 mA is possible with all input chan-

nels active, the 411 communicating, the Programmer con-
nected, and Lamp Test active.

Channels/Inputs

— TB2 Terminals 1 through 6:

• Programmable Channels 1 through 3.
• Power-limited circuitry.
• Fully supervised.
• Operation: All channels NFPA Style B (Class B). Requires

Normally Open contact to trigger.

• Normal operating voltage: 12 VDC.
• Maximum line resistance: 100 ohms per channel.
• Alarm current: 3.34 mA.
• End-of-line resistor: 2.2K ohms, 1/2 watt (P/N 27070).
• Short circuit current: 3.8 mA per channel/input.

NOTE: Channels/inputs do NOT support two-wire smoke

detectors.

Agency Listings and Approvals

These listings and approvals apply to the modules specified in

this docusment. In some cases, certain modules or applica-

tions may not be listed by certain approval agencies, or listing

may be in process. Consult factory for latest listing status.

UL Listed: S2424.

ULC Listed: S2424.

MEA Listed: 328-94-E Vol. III (411UD); 328-94-E Vol. IV

(411).

CSFM: 7300-0075:0174.

FDNY: COA#6085.

Product Line Information

411: Three-channel, dual-line, slave Digital Alarm Communi-

cator Transmitter. Includes housing, operating and program-

ming instructions. Requires PRO-411 hand-held DACT

programmer for local programming.