Vulcain 301w wireless gas detection network, Technical summary, User friendly – Notifier Vulcain 301W User Manual

Page 2: Easy and inexpensive to install, Few requirements - simple operation, Input/output adaptability, Safety measures, Beneficial controller options

Advertising
background image

Vulcain 301W

wireless gas detection

network

By removing the necessity for

expensive wiring and by greatly reducing
installation costs, the Vulcain 301W can cut
the bottom line for a parking garage’s CO
(carbon monoxide) monitoring system.

User Friendly

• Self-contained, wall mounted enclosure
• Simple push button operation

Easy and Inexpensive to Install

• Simply wall mount (no hardwiring required)
• Turn it on and the Vulcain 301W auto configures to the

controller and is fully operational

• Unobtrusive slim-line profile
• No mounting bracket required

Few Requirements - Simple Operation

• No calibration required for two years
• No monitor hardwiring required
• No battery replacement require for two years
• After two years, simply replace the easily removed

sensor/battery pack

Input/Output Adaptability

• Allows for up to 50 remote transmitters in the system

Safety Measures

• Virtually no false alarms—accurate and reliable
• Route redundancy, so if one link fails, communication

is automatically re-established through another monitor

• Avoids interference with Bluetooth, WIFI and other

wireless systems

• Secured 128 bit encrypted wireless mesh network
• Periodic ‘heartbeat’ signal ensures all transmitters are

continuously active

Beneficial Controller Options

• Datalogging option available
• Optional BACnet/IP Output

Zoning / Averaging

The Vulcain 301C controller offers unique zoning
capabilities which permit the averaging and
comparison of multiple sensor readings. Zoning can
reduce operational costs by ensuring that localized
brief fluctuations registered at a single transmitter
do not activate relays. For example, a car idling in
a parking structure may locally increase a reading
at a nearby transmitter. Rather than activating a fan
as a result of the temporary localized fluctuation,
zoning can be used to limit relay activation until the
average reading for a zone exceeds a set-point.
This can reduce run time of fans, yielding savings in
both energy usage and wear and tear. The Vulcain
301C has the capacity to manage input from three
Modbus channels for up to 96 transmitters and up
to 50 wireless transmitters which can be associated
with up to 126 zones. Transmitters can belong to
an unlimited number of zones, providing maximum
operational and control flexibility.

The Vulcain 301W wireless gas transmitter is
designed to detect carbon monoxide (CO) and
nitrogen dioxide (NO

2

) in parking structures or

oxygen (O

2

) in other applications. It operates for 2

years without calibration, maintenance or battery
replacement. The Vulcain 301W gas transmitter
exchanges data with the Vulcain 301C controller
over a wireless mesh network via a secured 128
bit encrypted communication protocol. In contrast
to traditional networks, this system offers greater
flexibility and operational reliability together with
significant installation and operational savings.
Without the need of monitor hardwiring, installation
costs are drastically reduced—simply wall mount
the Vulcain 301W transmitter, turn it on and it is
ready for operation.

Unlike point-to-point or point-to-multipoint
communication, if the communication path fails,
the system automatically finds an alternative
route. This enables continuous contact, even
in harsh environments. The inherent network
integrity combined with zoning capabilities and
electrochemical sensor accuracy minimizes false
alarms and ultimately trims operational costs.

Technical summary

Vulcain 301W General Specification

Uses

Wall mounted, wireless gas detector for carbon monoxide (CO) hazards, to be used in conjunction with

the Vulcain 301C controller.

Power Requirement

Battery operated with 2 years (minimum)

Size

22.5 x 10 x 5.7 cm (8.85 x 4 x 2.25 in.)

Weight

0.4 kg (0.88 lb.)

Sensing Technology

Electrochemical

Network Capacity

50 wireless transmitters to the Vulcain 301C

Visual Indicators

Two LEDs

Radius of Detection

15.24 m (50 ft.)

Calibration

Not required for 2 years

Communication Protocol

2.4 Ghz - IEEE 802.15.4 - Secured 128-bit encryption

Alarms

Centralized alarm management via Vulcain 301C wireless controller

Ratings and Certifications:

Conforms to

ANSI/UL 61010-1

Certified to

CAN/CSA C22.2 No. 61010-1

FCC Part 15 Subpart C(15.247)

RSS 210 Section 6.2.2(o)

Enclosure

NEMA 4X Polycarbonate – ABS

Vulcain 301C General Specification

Uses

Wall mounted gas detection control panel for the annunciation of gas hazards detected by the complete range of Vulcain

sensors (up to 50 Vulcain 301W transmitters) with relays for effective response to hazard(s) present (activation of ventilation

fans, audible and/or visual alarms, etc).

Power Requirement

17-27 Vac, 24-38 Vdc, 500 mA

Size

28 x 20.3 x 7 cm (11.02 x 7.99 x 2.76 in.)

Weight

1.1 kg (2.4 lb.)

Network Capacity

Three Modbus channels for up to 96 wired transmitters and up to 50 wireless transmitters

Optional BACnet capacity

Communication Line Lengths

Up to 609 m (2000 ft.) per channel

(RS-485)

T-Tap: 20 m (65 ft.), maximum per T-Tap

40 m (130 ft.) maximum for all T-Tap combined

30 m (100 ft.) between each 301W

Relay Output Rating

5 A, 30 Vdc or 250 Vac (resistive load)

Alarm Levels

3 fully programmable alarm levels

Time Delays

0, 30 sec., 45 sec., 1-99 minutes before and after alarm; latchable

Outputs

4 DPDT relays (alarms and/or fault); 65dBA buzzer

Display

Large 122 x 32 dot matrix display

Operating Humidity

0-95% RH, non-condensing

Operating Temperature

-20 to 50°C (-4 to 122°F)

Ratings and Certifications:

Certified to

CAN/CSA C22.2 No 61010-1

116662

Conforms to

ANSI/UL 61010-1

IEC 61010-1 Including Amendments A1:1992 +

A2:1995 and National Deviations (Canada, US)