Gas and steam, Electric (126 kw), Electrical service specifications (per dryer) – ADC AD-170SE User Manual

Page 26

Advertising
background image

22

2. Electrical Service Specifications

a. Gas and Steam Models Only

*

AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.

1/23/09

** 3-Wire is available.

b. Electric Models Only

*

AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.

1/23/09

** 3-Wire is available.

GAS AND STEAM

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.

C.

208 VAC AND 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY.

Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY. For others, calculate/verify
correct breaker size according to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

MINIMUM

WIRE SIZE

FUSING

CIRCUIT

BREAKER

Dual Element

Time Delay

60 Hz

50 Hz

208

3

28.3

*

50

50

230

3

31.9

*

50

50

240

3

26.7

*

45

45

380

3

16.2

*

25

25

380

4**

16.1

*

25

25

400

4**

16.1

*

25

25

416

4**

16.0

*

25

25

440

3

14.4

*

20

20

460

3

13.9

*

20

20

480

3

13.9

*

20

20

575

3

11.4

*

20

20

ELECTRIC (126 kW)

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.

C.

208 VAC AND 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY.

Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others, calculate/verify correct breaker
size according to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

MINIMUM

WIRE SIZE

FUSING

CIRCUIT

BREAKER

Dual Element

Time Delay

60 Hz

50 Hz

416

4**

191

*

300

300

460

3

172

*

225

225