Installation Guide APC BC300 Series 40kW 208/450/480V UPS

990-1401

Installation

3.3.4 Single Line Diagram for BC300

Figure 7 Single Line Diagram 208V

NOTICE!

Always keep AC, DC and communication cables separated.

NOTICE!

The grounding electrode conductor (Protective Earth - PE) must be the same size (ampacity) as
the UPS input circuit conductors. Conduit is not an acceptable grounding electrode conductor -
see National Electrical Code Section 250-91(a).

NOTICE!

The unit is wired from the factory as a separately derived system. Output neutral is bonded to
equipment ground through main bonding jumper inside the UPS. See National Electrical Code
Article 250-5(d) and 250-26 for correct installation grounding.

Notes:
1. Must be 3- or 4-wire.
2. Must be 3 or 4 cabling provided by others.
3. Input overcurrent protection is based on

80% rating - any deviation, please contact
APC.

4. F1, F2, F3 = 120A
5. F4, F5, F6 = 170A
6. All AC power cabling is 3- or 4-wire +

Ground at 208VAC 3-phase.

7. UPS output cables and input cables must

be in separate conduits.

8. Power wiring and control wiring must be in

separate conduits.

9. See installation manual for battery

information.

10. Installation must comply with all applicable

national and local codes.

Utility Source (provided by others)

208V 3 or 4 Wire + Ground

MIB

Service
Bypass
Panel

F4, 5, 6

UIF

Q001

UIS

UPS

F1, 2, 3

UOF

Q002

UOS

Q003

BS

UPS System Output

208V 3 or 4 Wire + Ground

111A

40kW

111A

111A

161A

161A

200AT

200A

250AT