Part 1 installation, Part 1 installation continued, Vi piping continued – Midco Economite RE4400DS User Manual

Page 6

Advertising
background image

6

? When the burner is installed in the vestibule of jacketed equipment, it is recommended
that the Automatic Safety Shut-Off Valves be left adjacent to the burner within the vestibule
and the Main Manual Shut-Off Valve be installed outside.

? Run full size pipe or tubing from regulator vent openings to outside of building. Provide no
traps in the vent lines and terminate away from all doors and windows; also make provisions
for keeping rain and foreign objects from entering the vent piping.

? When high supply gas pressure is encountered, as in the case in many industrial plants,
the gas line size can be reduced to allow for a greater pressure drop; however, the size must
be sufficient to deliver burner rating pressure.

CAUTION: High gas pressure supply lines require the proper pressure

reducing regulators. Install a high pressure regulator of the Tight Shut-Off type, sized
for main gas input, upstream of the low pressure regulators.
? The high pressure regulators must be adjustable to 14" W.C. outlet pressure.

? When the gas supply line is about to be put into service it must be tested to insure that it
is gas tight. Use air or inert gas under pressure and test with soap and water to locate leaks.
? Before gas is turned onto the system, a check must be made to see that there are no open
fittings and to make sure the burner main valve is closed.

? After checking for leaks, purge the gas line up to the burner inlet. Purging the air from the
gas supply line at this step will expedite the first light-off.

NOTE: If there is more than 1.0" W.C. differential in the inlet pressure to the burner

compared to when all other gas utilization equipment are off, refer to Section VII.

____________________________

Part 1

Installation Continued

Part 1 Installation

Figure 6: Piping Diagram

Natural Gas capacities
shown are for a total
pressure drop of 0.3"W.C.
For 0.5"W.C. pressure drop,
multiply capacity shown by
1.3. Propane capacities
shown are for a total
pressure drop of 0.5”W.C.
For higher permissible
pressure drops, consult
your gas supplier.

Table 2: Schedule 40 NPT

Pipe-Capacity Chart

10

200

590

400

40

275

200

500

450

650

75

190

150

360

325

475

20

150

400

275

Pipe
Size

3/4

3/4

1

1

1 1/4

1 1/4

1 1/2

Natural

Propane

Natural

Propane

Natural

Propane

Natural

100

160

300

275

630

400

Approximate Capacity -MBH

Pipe Length

Type

of Gas

VI

Piping

Continued

Advertising