Iv chimney, vent connector and draft control – Midco E20BP User Manual

Page 3

Advertising
background image

-3-

FIGURE 2 Wet Base Boiler with Unlined

Combustion Chamber

Maximum Firing Rate

100 MBH

143 MBH

195 MBH

225 MBH

Vent Pipe Diameter

5"

6"

7"

8"

TABLE 1 Recommended Vent Pipe Sizes

FIGURE 3 Draft Hoods

CAUTION: In no case should the burner tube be

allowed to extend into the chamber proper; it must be set at
least 1" short of the inside surface.

Special heat resistant alloy extension tubes and instructions

are available for those applications where the burner tube is too
short to reach the combustion chamber (such as old-fashioned
gravity warm air furnace installations).

WARNING: BURNER CABINET MUST BE MOUNTED IN

ORIENTATION SHOWN IN FIGURES 1 AND 2. ANY OTHER
MOUNTINGS MAY CAUSE A DANGEROUS CONDITION,
AND WILL VOID BURNER WARRANTY AND AGENCY
APPROVALS. NON-STANDARD ARRANGEMENTS MAY BE
AVAILABLE FOR SOME MODELS - CONSULT FACTORY
FOR DETAILS IF REQUIRED.

Before permanently setting the burner in place, check that the

nozzle ribbon and pilot assembly are free of foreign materials,
and also that the spark electrode assembly has not been
damaged or displaced. See Figure 6.

IV CHIMNEY, VENT CONNECTOR AND

DRAFT CONTROL

WARNING: The chimney shall be inspected for unsafe

conditions such as deteriorated masonry and excessive
soot or other blockage or potential blockage. Installation
must conform with local codes or in the absence of local
codes with ANSI Z21.8
latest edition and NFPA, ANSI Z223.1
latest edition.

WARNING:

THE VENT CONNECTOR SHALL NOT BE

CONNECTED TO A CHIMNEY ALREADY VENTING SOLID
FUEL BURNING EQUIPMENT, AN INCINERATOR OR AN
OPEN FIREPLACE.

The Vent Connector shall be made of non-combustible,

corrosion resistant material capable of withstanding the vent gas
temperature produced by the gas utilization equipment and of
sufficient thickness to withstand physical damage.

The Vent Connector shall be as short as possible. The

entire length shall be readily accessible for inspection, cleaning
and replacement.

The length of horizontal uninsulated Vent Connector

between chimney and a single gas utilization equipment shall
not exceed 75% of the height of the chimney above the
connector, or 100% if the Vent Connector is insulated.

The Vent Connector shall be installed so as to avoid turns or

other construction features which create excessive resistance
to flow of vent gas. It shall be installed without any dips or
sags and shall slope upward at least 1/4" per foot.

A manually operated damper shall not be placed in the Vent

Connector or chimney of any gas utilization equipment.

The Vent Connector shall be firmly attached to draft hood

outlets and flue collars. Joints between sections of connector
piping shall be fastened by sheet-metal screws or other
approved means. The Vent Connector shall be supported for
the design and weight of the material employed to maintain
clearance and prevent physical damage and separation of
joints.

A draft hood or a barometric draft regulator shall be installed

in the same room or enclosure as the equipment in such a
manner as to prevent any difference in the pressure between
the hood or regulator and the combustion air supply. In no
case shall the relief opening of the draft hood or barometric
draft regulator be located at a point lower than the top of the
highest flue passage in the equipment.

Gas utilization equipment requiring controlled draft may be

equipped with a listed double acting barometric draft regulator,
installed and adjusted in accordance with the manufacturerÕs
instructions, if approved by Local Codes.

A device which will automatically shut off gas to the burner

in the event of sustained backdraft is required. It shall be of the
listed manual reset type and installed and adjusted by a
qualified service technician in accordance with the
manufacturerÕs instructions.

FIGURE 4: Barometric Dampers

Figure 3 and 4: Copyright by the American Gas

Association. Used by permission of the copyright holder.