Specifications – Clary SP1250 LE User Manual

Page 15

Advertising
background image

Page 15

SPECIFICATIONS

ELECTRICAL

Input

Voltage

120VAC 85VAC to 155VAC (without Battery discharge)

Frequency

45Hz to 65Hz

Output

Voltage

120VAC +3%

Frequency

50Hz or 60Hz +.25% (software selectable)

Current

SP560

SP1250LE

4.8 A (400W / 570VA)

10.4A (875W / 1250VA)

Crest Factor Ratio
(Non-linear load and
less than 5% THD) Typical

@50% Load Up to 4.8:1
@75% Load Up to 3.2:1
@100% Load Up to 2.4:1

Harmonic Distortion

3%

Dynamic Response

+4% for 100% Step Load Change, 0.5 Millisecond Recovery Time

Overload

110% for 10 min; 200% for 50 milliseconds

Efficiency (UPS)

Load Power Factor

85%

0.7

UPS Protection

Input and Output Short Circuit; Input and Output Overload;
Excessive Battery Discharge

MECHANICAL

Input (Qty)

(1) IEC Inlet C14

Output (Qty)

SP560

SP1250LE

(1) IEC Outlet C13

(2) IEC Outlet C13

Overall Dimensions W x D x H

SP560

SP1250LE

11in x 8.5in x 1.7in

15.25in x 8.5in x 1.7in

Weight

SP560

SP1250LE

5 lb. (2.3 kg)

8 lb. (3.6 kg)

Cooling

Low Velocity, Forced Air

CONTROLS AND INDICATORS

Visual Indicators

Battery Status, AC Output, Alarm, AC Input

Controls

Load On/Off, Cold Start

Intelligent Computer Interface

(1) DB9-F – RS232/Signal Interface

(1) USB Type B

DESIGN

Standard Features

Regenerative On-Line, Sinewave Inverter Powers Load Continuously,
Extended Brownout Protection, External Battery Connector, Digitally
Controlled IGBT PWM, Power Factor Corrected on Input, Designed for
Non-linear Loads

ENVIRONMENTAL

Operating Temperature

-40

o

F to 165

o

F (-40

o

C to 74

o

C)

Humidity

0% to 95% non-condensing

Altitude

Sea Level to 10,000 Feet

Advertising