2.2 Specifications

SP170-PDA W/UPS MODULE

ELECTRICAL
Input

Voltage 120VAC

+12%(135VAC),

-

25%(90VAC)
(before battery use)

Frequency

48 to 62Hz

Current (1250, 1250(PLUS),
2000)

8.8A, 8.8A, 14.3A

Power Factor Corrected

Output

Voltage

120VAC

± 3%

Frequency

50Hz / 60Hz (software select)
Line Sync (software select)

Rating:

SP170-PDA/1250

1250 VA/875 Watts, 10.4A

SP170-PDA/1250(PLUS)

1250 VA/875Watts or 1400 watts
for 10 seconds, 10.4A

SP170-PDA/2000

2000 VA/1400Watts, 16.7A

Total Harmonic Distortion (THD)

3% Typ; 5% Max.
(@100% Non-linear load)

Dynamic Response

±4% for 100% Step Load Change,
0.5 Millisecond Recovery Time

Overload

110% for 10 Minutes;
200% for 50 milliseconds

UPS Protection

Input and Output Short Circuit;
Input and Output Overload;
Excessive Battery Discharge

Output DC

Voltage

24.0 VDC, +3%

Current

0 – 5.0 amps

ENVIRONMENTAL

Operating Temperature

-40

o

C to +74

o

C (-40

o

F to +165

o

F)

Humidity

0% to 95% Non-condensing

Altitude

Sea Level to 10,000 Feet

(some derating of temp.

w/altitude > 6000 ft)

MECHANICAL

Input

Hardwired to Input Terminal

Outputs

Hardwired to Output Terminal

Dimensions (H x W x D) in.

7.0 x 19.0 x 16.0

Weight (lbs)

30

DESIGN

Standard Features

Power Factor Corrected Input;

Fully Regenerative;

True On-Line Continuous Power;

Low Distortion Sinewave Ouput;

Designed for Non-linear Loads;

Extended Brownout Protection;

EIA/RS232 Data Interface;

Specifications

Meets FCC Class A, IEEE

587/ANSI C62.41, IEC 555 @

120 VAC and NEMA Stds.

MTBF

Inverter: > 100,000 hrs.

System w/Bypass: 150,000 hrs

Calculated from Component Spec.

Typical Recharge Time to
85% Capacity at 100% Load

48-72 hrs (more time required with
extended battery option)

Less than 20 hrs with optional Fast
Battery Charger.

CONTROLS AND INDICATORS

LCD Display

System Set-up and System Status
Features including Day and Date,
System Load Level, Battery System
Status and Event Logs.

Controls

Power On; Cold Start; Test; Alarm
Silence; LCD Controls

Audible Alarms

Utility Interrupt; Inverter Failure;
Overload; Low Battery; Self Test

Serial Interface for EIA 232.
Optional NTCIP and TCP/IP via
Standard RJ45 Connector

Full Interactive, Remote Computer
Monitoring and Control of UPS
Functions.

Compatible with Systems Enhancement
UPS Monitor & Control Software

Open-Collector (DB-9F)

Open Collector for Remote
Annunciation of Power Up, Power
Down, On Battery and Low Battery.

Relay Contacts

Normally Open/Normally Closed

4 sets available; can be configured for
various settings; On Batt, Timer,
Battery Capacity, Alarms etc..

Specifications subject to change without notice.

01/2008