SIGNALS AND INTERFACING

This system is designed to be compatible with most sophisticated operating systems when they
feature a UPS monitoring function. These signals are made available through the DB-25
subminiature female connector at the rear of the Control Panel. Interfacing cables are available.
The communications connector at the rear of the UPS is for a RS232 interface connection. The
Remote Panel connector features open-collector alarm signals. Closing the points between pins
6 and 8 while running on battery will shutdown the UPS. Below is a diagram of the signal jacks
and their pin-outs:

RS232 CONNECTOR

1-

LOW BATT

2- TX

3- RX

4- DTR

5- SIGNAL

GROUND

6- DSR/+9V

7- RTS

IN

8-

AC INPUT FAIL


NOTE: Pin 4 enables a relay on the

Interface board that allows communications

directly with the UPS from the RS232

Connector. When relay is enabled, SNMP

is disabled.

REMOTE PANEL CONNECTOR ON THE

REAR OF THE CONTROL PANEL

2 & 14- AC INPUT FAIL

3- UPS

ON

4 & 15- GROUND

5 & 9- LOW BATTERY

6-

REMOTE SHUTDOWN+

7-

+9VDC

8-

REMOTE SHUTDOWN (RETURN)

13 9 8 7 6 5 4 3 2 1

25 15 14

AC INPUT FAIL

UPS ON

REMOTE +

1K

SHUTDOWN -

LOW BATTERY

GND

+9V

+9V

1K

1K

+9V