User configuration items, How to determine on-battery run time – APC 1400XLT User Manual

Page 22

Advertising
background image

990-7031D, Revision 5 5/01

16

User Configuration Items

Note: Setting these items requires optional software or hardware.

Function

Factory Default

User Selectable Choices

Description

Automatic Self-Test

Every 14 days
(336 hours)

Every 7 days (168 hours), On
Startup Only, No Self-Test

Sets the interval at which the UPS will execute a self-test.

UPS ID

UPS_IDEN

Up to eight characters to define
the UPS.

Use this field to uniquely identify the UPS for network
management purposes.

Date of Last Battery Replacement

Manufacture Date

Date of Battery Replacement

Reset this date on battery replacement.

Minimum Capacity Before Return from
Shutdown

0 percent

15, 50, 90 percent

The UPS will charge its batteries to the specified percentage
before return from a shutdown.

Sensitivity

Normal

Reduced, Low

Set lower than normal sensitivity to avoid lowered battery
capacity and service life in situations where the load can
tolerate minor power disturbances.

Duration of Low Battery Warning

2 minutes

5, 7, 10 minutes

Sets the time before s hutdown at which the UPS issues a low
battery warning. Set higher than the default only if the OS
needs the time for graceful shutdown.

Alarm Delay After Line Fail

5 second delay

30 second delay, At Low
Battery Condition, No Alarm

To avoid alarms for minor power glitches, set the alarm delay.

Shutdown Delay

20 seconds

180, 300, 600 seconds

Sets the interval between when the UPS receives a shutdown
command and when shutdown occurs.

Synchronized Turn-on Delay

0 seconds

60, 180, 300 seconds

To avoid branch circuit overload, the UPS will wait the
specified time after the return of utility power before turn-on.

High Transfer Point

229

224, 234, 239

To avoid unnecessary battery usage, set the High Transfer
Point higher if the utility voltage is chronically high and the
load is known to work well under this condition.

Low Transfer Point

177

168, 172, 182

Set the Low Transfer Point lower if the utility voltage is
chronically low and the load can tolerate this condition.

How to Determine On-Battery Run Time

Note:

UPS battery life differs based on usage and environment.

APC recommends that the battery/batteries be changed once every two years.

Tower and 5U Models - 1400VA and 2200VA Models

Typical On-Battery Runtime Versus Load, in Hours

Load
(VA)

Internal
Battery

1

Battery

Pack

2

Battery

Packs

3

Battery

Packs

4

Battery

Packs

5

Battery

Packs

6

Battery

Packs

7

Battery

Packs

8

Battery

Packs

9

Battery

Packs

10

Battery

Packs

100

4.50

9.75

15.42

21.08

26.75

32.42

38.08

43.75

49.41

55.08

60.75

200

2.75

6.25

9.75

13.50

17.25

21.08

24.83

28.58

32.33

36.17

39.92

300

1.83

4.50

7.08

9.67

12.50

15.33

18.08

20.92

23.75

26.58

29.42

400

1.33

3.42

5.42

7.50

9.58

11.83

14.08

16.33

18.58

20.75

23.00

500

1.05

2.67

4.42

6.08

7.83

9.50

11.33

13.25

15.08

16.92

18.75

600

0.85

2.17

3.67

5.08

6.50

8.00

9.42

11.00

12.58

14.17

15.75

700

0.68

1.75

3.00

4.25

5.50

6.75

8.00

9.26

10.67

12.00

13.33

800

0.58

1.50

2.58

3.75

4.83

5.92

7.08

8.17

9.25

10.50

11.67

900

0.48

1.27

2.25

3.25

4.25

5.25

6.25

7.25

8.25

9.17

10.25

1000

0.43

1.12

2.00

2.83

3.75

4.67

5.58

6.42

7.33

8.25

9.17

1200

0.33

0.88

1.52

2.25

3.00

3.75

4.50

5.25

6.00

6.75

7.50

1400

0.27

0.70

1.22

1.83

2.50

3.08

3.75

4.42

5.00

5.67

6.25

1600

0.22

0.57

1.00

1.47

2.00

2.58

3.08

3.67

4.17

4.75

5.25

1800

0.18

0.48

0.87

1.25

1.75

2.17

2.67

3.17

3.67

4.17

4.67

2000

0.15

0.42

0.73

1.08

1.45

1.92

2.33

2.75

3.17

3.67

4.08