SPECIFICATIONS (Preliminary)

ELECTRICAL

Input
Voltage

120VAC +35%, -20%

Frequency

60Hz or 50Hz

Current

20A Max @ 120VAC

AC Output
Voltage(AC)

120VAC +3%

Current, Watts

1250VA(875W) @ 0.7pf

Frequency

60Hz or 50Hz +.25% (software selectable)

Crest Factor Ratio
(Non-linear load and
less than 5% THD) Typical

@50% Load Up to 4.8:1
@75% Load Up to 3.2:1
@100% Load Up to 2.4:1

Harmonic Distortion

5% Max. THD

Dynamic Response

+4% for 100% Step Load Change, 0.5 Millisecond Recovery Time

Overload

110% for 10 Minutes; 200% for 50 milliseconds

Efficiency (UPS)
Load Power Factor

85%
0.7

UPS Protection

Input and Output Short Circuit; Input and Output Overload;


CONTROLS AND INDICATORS

Visual Indicators

Battery Level, Load Level, AC Input, Inverter, Battery On, Bypass On,
Cold Start, Fault, Replace Battery

Audible Alarms

Utility Interrupt, Inverter Failure, Overload, Low Battery, fan fail, warm and
overtemp.

Intelligent Computer Interface
(DB-25F)

Full Interactive, Remote Computer Monitoring and Control of
UPS Functions (RS232 Interface);
Open-collector Alarm Signals interface to control panel

DESIGN

Standard Features

Regenerative

TM

On-Line, Sinewave Inverter Powers Load Continuously

Extended Brownout Protection, High Frequency, Digitally Controlled IGBT
PWM, Power Factor Corrected on Input, Designed for Non-linear Loads,
Continuous Operation on +35% Line

ENVIRONMENTAL

Operating Temperature

32

o

F to 122

o

F (0

o

C to 60

o

C)

Humidity

0% to 95% non-condensing

Altitude

Sea Level to 10,000 Feet

MECHANICAL

Input

L5-30P Inlet connector

AC Output (AC1-AC8)

(8) NEMA 5-15R connectors

Overall Dimensions L x H x W

18.5 in x 5.25 in x 19 in.

Weight

40lb. (18.2 kg)

Cooling

Low Velocity, Forced Air