Ashcroft P-N7 pressure switches User Manual

Switches/low voltage directive 73/23/eec

Advertising
background image

INSTALLATION REQUIREMENTS
• To minimize the risk of injury, the switch enclosure must be

selected according to the area classification and installed
according to the required safety and electrical codes.

• Before operating the switch all conduit entries and/or junction

boxes need to be closed according to the required safety and
electrical codes.

• To attain the degree of protection listed on the switch it may

be necessary to add required conduit fittings.

• The switch must be protected from moisture, shock and/or

extreme vibration.

• The ambient temperature limits for switches are –20 to 150°F,

(–28 to 65°C).

CAUTIONS
• Always install the cover after wiring the switch and before

power is supplied.

• Before removing the cover in hazardous areas be sure there

is no explosive atmosphere present and the power supply is
turned off.

• For ATEX approved switches all safety locking devices and

electrical earthing must be installed or connected before
operating.

• Never carry a temperature switch by holding only the stem,

bulb or capillary.

• Do not exceed ranges, current and/or voltage limits.
• The protection degree of the switch is only valid when the

switch is installed in accordance with all safety and electrical
codes and regulations.

CLEANING
• Never use aggressive solvents.
• Do not use high pressure water to clean the switch.

MAINTENANCE/TROUBLESHOOTING
• All Ashcroft switches require little or no maintenance.
• Be sure that the case is closed at all times.
• When the switch is exposed to process media that may hard-

en and/or build up in the pressure port, the switch should be
removed and cleaned as needed.

• If the switch does not function, only trained and skilled per-

sonnel should check on the wiring, power supply and/or
mounting.

• If the problem can not be solved, please contact one of the

Ashcroft affiliates or distributors.

ELECTRICAL CONNECTIONS
• Only trained and skilled personnel are allowed to install the

wires to the electrical terminals of the switch.

• Cable couplers, glands and conduit connectors must have the

correct electrical approvals.

• Always follow safety and electrical regulations when connect-

ing these devices.

• The system ground of the device is marked with a green

colored screw and/or by the ground symbol.

• ATEX approved switches have an external ground screw that

must be connected.

• Micro switch terminals and wire color codes:

NO

(Normally Open)

Blue

NC

(Normally Closed)

Red

C

(Common)

White

Ground

Green (F-Series only)

MICRO SWITCH CODE

ELECTRICAL RATING

Single

Dual

Single

Dual

Vac

Vdc

K

KK

20

61

15A, 250V

0.4A, 120V

W

WW

21

65

5A, 250V

6A, 30V

P

PP

22

67

5A, 250V

2.5A, 28V

C

N/A

23

N/A

22A, 250V

G

GG

24

64

15A, 480V

0.25A, 250V

S

N/A

25

N/A

10A, 125V

10A, 125V

F

FF

26

62

15A, 250V

0.4V, 120V

Y

YY

27

63

15A, 250V

U

UU

28

N/A

15A, 250V

6A, 30V

E

EE

29

N/A

15A, 250V

6A, 30V

M

MM

31

70

1A, 125V

50mA, 60V

J

JJ

32

68

11A, 250V

5A, 30V

L

LL

42

71

1A, 125V

N/A

N/A

50

N/A

15A, 250V

H

HH

35

N/A

10A, 250V

0.25A, 250V

© 2007 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M009-10030-10/00 (250-3136) AMR 5/07

Installation and Maintenance
Instructions for CE Mark on ASHCROFT

®

Switches/Low Voltage Directive 73/23/EEC

TABLE 1: MICRO SWITCH ELECTRICAL RATINGS

Advertising