Ashcroft GT - Temperature Switches User Manual

Page 2

Advertising
background image

ELECTRICAL CONNECTION
Remove cover, held in place by four screws.

On all units except one with terminal blocks – wire directly to

the switch according to circuit requirements. Units with terminal
blocks – wire directly to terminal blocks as required. Terminals
are marked common (C), normally open (NO) and normally
closed (NC).

SETPOINT ADJUSTMENTS
Setpoints are changed by means of the setpoint adjusters. The
GT-S single switch has one adjuster and the GT-A adjustable
dead band and GT-D dual switch each have two adjusters. On
switches with two adjusters, the one on the left is referred to as
“A” and the right one is referred to as “B”; see illustration.
Setpoints can be adjusted from 20 to 100 percent of full range
on increasing temperature.

When adjusting temperature controls optimum performance

will be obtained if the bulb is fully immersed. After initially insert-
ing a bulb into a controlled bath, allow five minutes for stabiliza-
tion. Whenever setpoint adjustment requires a bath temperature
to be varied (such as to observe setpoint and re-setpoint values)
the rate of change in temperature should not exceed 1 0F per
minute. Switch operation should be monitored with a suitable
light or meter.

Installation and Maintenance Instructions
for ASHCROFT

®

G-Series Snap Action

Switches for Temperature Control

A

B

0

20

40

60

0

20

40

60

1

2

3

1

2

3

LEFT SWITCH

TERMINAL BLOCK

RIGHT SWITCH

TERMINAL BLOCK

SERVICE LEADS TO THESE TERMINALS

NC

NO

C

SERIES GT-S SINGLE SWITCH
Remove cover. For setpoint adjustment on either increasing or
decreasing temperature, the bulb of the control should be
immersed in a bath at the desired setpoint temperature. Opti-
mum performance will be obtained if bulb is fully immersed.
Allow five minutes for initial stabilization. Monitor switch with a
light or meter.

If setpoint is on increasing temperature, turn adjuster so that

switch operates (if common – normally closed circuit is being
monitored light goes off). If setpoint is on decreasing tempera-
ture, turn adjuster so that switch resets (if common – normally
closed circuit is being monitored light comes on). When the
setpoint has been achieved, raise and lower the temperature to
ensure that the setpoint is correct.

The deadband (difference between the operate and reset

temperatures) may be verified at this time to be between the
values noted on the nameplate label.

SERIES GT-D DUAL SWITCH
Remove cover. Immerse the bulb and monitor the switch as
described under Series GT-S Single Switch. Also see discus-
sion of increasing or decreasing setpoints and deadband verifi-
cation. The initial bath temperature should be the higher set-
point. Turn adjuster “B” until the switch operates or resets as
required. When the setpoint has been achieved, raise and lower
the bath temperature to ensure that the setpoint is correct. Then
reduce the bath temperature to the lower setpoint and turn
adjuster “A” until the switch operates or resets as required.
Verify this setpoint by raising and lowering bath temperature.
Now increase the temperature to the higher setpoint and make
final adjustment on “B.”

SERIES GT-A ADJUSTABLE DEADBAND SWITCH
Remove cover. Adjuster “B” controls the operating point of the
switch on increasing temperature. Adjuster “A” controls the re-
setpoint of the switch on decreasing temperature.

Immerse the bulb and monitor the switch as described under

single switch setpoint adjustment. With the bath at the required
setpoint temperature, turn adjuster “B” until switch operates.
Then lower the bath temperature to the re-setpoint and turn
adjuster “A” until the switch resets. Now increase the tempera-
ture to the operating point and make final adjustment on “B.”
Raise and lower temperature to ensure that the setpoint and
re-setpoint are correct.

SOME PRECAUTIONS TO OBSERVE
Do not loosen the screws holding the precision switch element(s)
or mounting bracket in place.

Nameplate PROOF temperature should not be exceeded.

Intermittent operation up to proof temperature is permissible,
however, some change of setpoint may be noted.

Operation and correct setpoint actuation should be routinely

tested.

© 2007 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M009/10022-10/00 (250-2894) AMR 12/07

Advertising