Horner APG RX371 OCS HERX371C101 User Manual

Page 4

Advertising
background image

MAN0925-02-EN

Specifications / Installation

________________________________________________________________________________________________________________________________________
6/1/11 Page 4 of 5 # 1018

4.2

Ethernet Port

Table 3 - Ethernet Port

Speeds

10 BaseT Ethernet (10-Mbps)

100 BaseTx Fast Ethernet (100-Mbps)

Modes

Half or Full Duplex

Auto - Negotiation

Both 10/100-Mbps and Half/Full Duplex

Connector Type

Shielded RJ-45

Cable Type (Recommended)

CAT5 (or better) UTP

Port

Auto MDI/MDI-X









4.3 External DIP Switch settings

















4.4 CAN Network Port and wiring

4.5 Power port and wiring














Table 2 - Ports and Functions

Functions

Port 1 (MJ1)

Port 2 (MJ2)

RS-232

!

!

Hardware Handshaking

!

X

Programming

!

X

Ladder function controlled

!

!

Serial Downloadable
Protocols

!

!

RS 485 Half duplex

!

!

RS485 Full duplex

X

!

NET 1 Port Pin Assignments

Pin

Signal

Signal Description

Direction

1

V-

CAN Ground

-

2

CN_L

CAN Data Low

In/Out

3

SHLD

Shield Ground

-

4

CN_H

CAN Data High

In/Out

5

NC

No Connect

-

Primary Power Port Pins

Pin

Signal

Description

1

Ground

Frame Ground

2

V-

Input Power Supply Ground

3

V+

Input Power Supply Voltage

As seen when looking at the side of the RX371 unit:


The DIP Switches are used for
termination of the RS-485 ports. The
RX371 is shipped un-terminated.


To terminate, select one of the DIP
Switches and configure it based
upon the option that is desired.

MJ1

On

Off
On

Off
On

Off

MJ2

SW1 –
ON enables MJ2 RS485 port termination (121 ohms)
OFF disables MJ2 RS485 port termination.

SW2 & SW3 –
ON places MJ2 RS485 port in half-duplex mode.

OFF places MJ2 RS485 port in full-duplex mode.

SW4 –
ON enables MJ1 RS485 port termination (121 ohms)
OFF disables MJ1 RS485 port termination.

CAN Connector

Use the CAN Connector when

using CsCAN network.

Torque rating 4.5 – 7 Lb-In

(0.50 – 0.78 N-m)


Power Connector

Power Up:

Connect to Earth Ground.

Apply 10 - 30 VDC.

Screen lights up.

Torque rating 4.5 – 7 Lb-In

(0.50 – 0.78 N-m)