Horner APG SmartStack I/O HE-RTD100* User Manual

Rtd input module, 1 specifications

Advertising
background image

MAN0236-09

10 NOV 2006

PAGE 1

RTD000/100

This Data Sheet is published individually & also as a part of the SmartStack Supplement (SUP0246-05).

Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.

This datasheet also covers products starting with IC300.

1 SPECIFICATIONS

RTD000

RTD100

RTD000

RTD100

Number of Channels

2 4

Required

Power

(Steady State)

0.10W (4.2mA @ 24VDC)

Required

Power

(Inrush)

Negligible

RTD Types

100, 200, 500, 1000 Ohms
at 0

°C, Platinum, Alpha

0.00385, DIN43760

Average RTD
Current

0.44mA (100 Ohm Range)

Input Range

-200

°C to +850°C

I/O Points Required

2 4

Input Impedance

>100Meg Ohm 0-4VDC

Clamped @ 0 and 4VDC

Converter Type

Integrating

RTD Excitation Current

2.2, 1.1, 0.44, 0.22mA, 25%

duty cycle

Types Supported

DIN43760

Accuracy

± 0.5°C

RTD Short

Indefinite

Resolution

0.05

°C

Channel-to-Channel
Tracking

0.1

°C

Update Time

16 channels/second

Operating
Temperature
Relative Humidity

0

° to 60° Celsius

5 to 95% Non-condensing

Input Transient
Protection

Zener/Capacitor

Terminal Type

Spring Clamp, Removable

Notch Filter

50-60 Hz. Software

Selectable

Weight

9.5 oz. (270 g)

CE

UL

See Compliance Table at

http://www.heapg.com/Support/compliance.htm

RTD Input Module

HE800RTD000 / HE800RTD100

HE-RTD000 / HE-RTD100*

* HE- denotes plastic case.

Advertising