Horner APG SmartStix HE559ADC970 User Manual

Smartstix, Analog input module

Advertising
background image










Refer to SmartStix Analog Programming Guide (MAN0703) at

www.HornerOCS.com

.


1

SPECIFICATIONS

ANALOG IN

Number of input
points

12

Additional error for
temperatures other
than 25°C

0.01% /

°

C

Input Ranges

±5, ±10V DC

4-20, ±20mA DC

Isolation

1000V DC

IEC61010-1 300V

RMS

Resolution

14 bits

Isolation Method

Magnetic

Accuracy, 25°C

0.1%

Input Impedance

V: 1 Megohm

mA: 150 Ohms

Maximum
Continuous
Overload

±10V: 150VAC

±20mA: ±30mA,
Clamped at ±6V

Register Value for
Nominal Full Scale

32000

Programmable Filter
Time Constants

0.01 to 1.28 Seconds

Conversion Time

10ms for all

Channels

Filter Modes

Running Average or

Adaptive

GENERAL
Required Power
(Steady State)

1.8W

(75mA @ 24VDC)

Pollution degree

2 or lower

Required Power
(Inrush)

8A @ 24VDC for

5ms

Operating
Temperature

0

°

to 55

°

C

Atmosphere

Free from corrosive

gases and excessive

dust

Storage Temperature

-25

°

to 70

°

C

Cooling method

Self-cooling

Operating and
Storage Humidity

5 to 95% Non-

condensing

Altitude for use

Up to 2,000m

Weight

8.0 oz. (227 g)








MAN0557-01

Analog Input Module

HE559ADC970

12 Input Channels

±5V / ±10V / 4-20mA / ±20mA

CsCAN

SmartStix

Advertising