Horner APG SmartMod HE359DAC107 User Manual

Smartmod analog output module, 1µ a or 1 mv resolution

Advertising
background image

MAN0838-04-EN

Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________

5/11/2009

Page 1 of 2 ECN # 950











1

Specifications

DAC007

DAC107

DAC007

DAC107

Number of

Channels

2

4

Auxiliary

Voltage

12V @ 20mA (4

channels)

Output

Ranges

0-20mA or 0-10V

Terminal

Type

Screw Type,

Removable

Resolution

1

µ

A or 1 mV

Storage

Temp.

-40

°

to 85

°

Celsius

Operating

Temp.

-10

°

to 60

°

Celsius

Load

Resistance

Voltage: >5Kohm

Current: <500ohm

Relative

Humidity

5 to 95% Non-

condensing

Output

Calibration

Voltage: +/-10mV

Current: +/-20uA

Dimensions

WxHxD

17.5mm x 100mm

x 120mm

0.69” x 3.94” x

4.72”

External

Power

Supply

Voltage

18-30Vdc

Weight

150g (6 oz.)

Required

Power

(Steady

State)

30mA @ 24Vdc,

typical

(100mA max)

Communica-

tions

Modbus/RTU

(binary)

RS-485 half duplex

Required

Power

(Inrush)

Negligible

Factory

Default

Communica-

tions

Parameters

38400 baud, N, 8, 1,

no h/s

Default Modbus ID 1

Isolation

2000Vac for 60

seconds

(Input/Power &

Input/Comms)

Supported

Modbus

Commands

(family)

1,2,3,4,5,6,8,15,16

CE & UL

Compliance

See Compliance Table at

http://www.heapg.com/Pages/TechSupport/ProductCert.html


2

Wiring – I/O


















































SmartMod

Analog Output Module

HE359DAC007 / HE359DAC107

Selectable 0-20mA or 0-10V

1

µ

A or 1 mV Resolution

Dimensions in inches are 0.69”W x 3.95”H x 4.72”D

Note: Number of I/O terminal connections vary from model to model

I/O

RS-485

DC IN

Pin

#

DAC007

DAC107

Pin

#

DAC007

DAC107

1

I

I

9

I

2

AUX

AUX

10

AUX

3

V

V

11

V

4

GNA

GNA

OUT 0

12

GNA

OUT 2

5

I

I

13

I

6

AUX

AUX

14

AUX

7

V

V

15

V

8

GNA

GNA

OUT 1

16

Only Terminals
1 through 8 are

present on the

DAC007 model

GNA

OUT 3

D-

D+

GND

INIT

A

B

C

D

V-

V+

I

J

10-30Vdc

Notes:
Both ends of the RS-485 network should be terminated with a 100ohm, 1/4W, 1% resistor. Many OCS controllers
feature dip switches or jumpers which enable appropriate termination if the OCS is located on a network end.

Wiring RS-485

Wiring DC IN

ACTIVE

LOOP

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

I

AUX

V

GNA

I

AUX

V

GNA

I

AUX

V

GNA

I

AUX

V

GNA

IN

0

IN

1

IN

2

IN

3

PASSIVE

LOOP

VOLTAGE

+

NOTE: EACH

CHANNEL MAY BE

WIRED

INDEPENDENTLY

Advertising