Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________

5/8/2009 Page 2 of 2 ECN # 950

3

Init Default Setup

Communication parameters will be set to INIT default after performing the procedure:

1. Install jumper between INIT and GND terminals of the RS-485 port.
2. Apply power to Smartmod unit.
3. Read parameter words to see current parameters.
4. Write changes if necessary.







The INIT Default RS485 Settings Are:
Modbus ID = 1
Baud rate = 9600
Parity = None
Stop Bits = 1
Data Bits = 8
No handshake




4 Configuration

DATA


SmartMod Configuration settings are mapped into Modbus Register space. This
configuration data may be modified with any Modbus/RTU Master device. For
convenience, Horner APG has developed a variety of Cscape application files which
allow an OCS (Xle, NX, LX, QX) to act as a SmartMod configurator. Initial
configuration of SmartMod module should be done on an individual basis, since all
modules come from the factory with a default Modbus ID of 1. Once each module on
the network has its own unique Modbus ID, further configuration adjustments can be
made with the entire network powered.

All configuration parameters listed below (except 40012 Channel Enable) are stored
in EPROM. That means they should not be constantly rewritten.

Configuration Parameters – Registers 40001 through 40013

Modbu

s

Regist

er

Description Min

Max

Default

40001-

40005

Reserved

40006

Communications Parameters

See Table

38.4kbaud, N, 8, 1,

RTU Mode

40007 Modbus

ID 1

255

1

40008

Rx/Tx Delay (in 2mS steps)

0

255

0mS

40009

Watchdog Timer (in 0.5s steps)

0

255

10 (5s)

40010

Modbus Coil Data

Not Configuration Data – See I/O

Data

40011

Input Type

6

6

6 (+/-20mA)

40012

Channel Enable

See Table

255 (Channels 1-

8 enabled)

40013 Reserved

Register 40006 (Communications Parameters) Bit Definition

Bits 7-15

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Unused Mode

Parity

Data

Bits

Baud Rate

Value Meaning

Value

Meaning

0 Mark

0

1200

baud

0 =

ASCII

Mode

1 Even

0 = 7

Data

Bits

1 2400

baud

2 Odd

2

4800

baud

3 Space

3

9600

baud

1 =

RTU

Mode

1 = 8

Data

Bits

4 19200

baud

5-7 38400

baud

Register 40012 (Channel Enable) Bit Definition

Bit 8-15

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Unused Input 1

Input 1

Input 1

Input 1

Input 1

Input 1

Input 1

Input 1

0 = Disable Input

1= Enable Input





5 Input/Output

DATA


SmartMod Analog I/O utilizes both Modbus Registers (40001-40030) and Coils (1-11). It is
possible to access all data using Registers only, because the Coils can be accessed through
Register 40010.

The following tables lists all Modbus I/O data available.

I/O Register Data (Registers 40014-40022)

Modbus

Register

Description Access

INIT

D-

D+

GND

A

B

C

D

Minimum Maximum

Units

40010

Mirror of Coil Data

Read/Write

n/a

n/a

n/a

40014

Cold Junction Temperature

Read-only

-1000

6000

0.01 degrees C

40015

Input 0

Read-only

-20000

+20000

1µA (0.001mA)

40016

Input 1

Read-only

-20000

+20000

1µA (0.001mA)

40017

Input 2

Read-only

-20000

+20000

1µA (0.001mA)

40018

Input 3

Read-only

-20000

+20000

1µA (0.001mA)

40019

Input 4

Read-only

-20000

+20000

1µA (0.001mA)

40020

Input 5

Read-only

-20000

+20000

1µA (0.001mA)

40021

Input 6

Read-only

-20000

+20000

1µA (0.001mA)

40022

Input 7

Read-only

-20000

+20000

1µA (0.001mA)

Modbus

Coil

Description

Access

Watchdog Event & Power-

up Event Operation

00001

Open Detect Input 0

Read/Write

00002

Open Detect Input 1

Read/Write

00003

Note: There are 2 types of default settings possible:
1. Factory default as described in section 1 (Specifications)
2. Default after INIT as described in section 3 (INIT Default Setup)

Open Detect Input 2

Read/Write

00004

Open Detect Input 3

Read/Write

00005

Open Detect Input 4

Read/Write

00006

Open Detect Input 5

Read/Write

00007

Open Detect Input 6

Read/Write

00008

Open Detect Input 7

Read/Write

00009 Watchdog

Enabled Read/Write

00010 Watchdog

Event Read/Write

00011 Power-up

Event Read/Write

If Coil 9 (Watchdog Enabled)

is set, Coil 10 (Watchdog

Event) will set if the Watchdog

Timeout value is exceeded.

The Watchdog Timeout value

is set in Register 40009.

When set, Coil 10 can be

reset by the controller when

normal communications

resumes.

The Power-up Event (Coil 11)

is set every time the power is

applied. It can be cleared by

the controller if desired.


6

Installation / safety



a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, twisted-pair wiring should be used for best performance.
c. Shields may be terminated at the module terminal strip.

Warning: Remove power from the OCS controller, CAN port, and any peripheral
equipment connected to this local system before adding or replacing this or any
module.

d. In severe applications, shields should be tied directly to the ground block within the panel.
e. Use the following wire type or equivalent: Belden 8441.

For detailed installation and a handy checklist that covers panel box layout requirements and
minimum clearances, refer to the hardware manual of the controller you are using.

When found on the product, the following symbols specify:






7 Technical

Support

Technical Support at the following locations:

Warning: Electrical
Shock Hazard.

Warning: Consult
user documentation.


North America:
Tel: 317 916-4274
Fax: 317 639-4279
Web:

http://www.heapg.com

Email:

[email protected]

Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web:

http://www.horner-apg.com

Email:

[email protected]


No part of this publication may be reproduced without the prior agreement and written
permission of Horner APG, Inc. Information in this document is subject to change
without notice.