Horner APG SmartRail HE599RTD100 User Manual

Smartrail, Rtd input module (pt-100), Prefer spring-clamps

Advertising
background image

MAN0937-02-EN

Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________
1/3/2011

Page 1 of 1










1

Specifications

Specifications

RTD100

Number of Channels

4

American (α=0.00392)

Japanese Std (α=0.003916)

Types Supported

DIN Std (α=0.00385)*

Temperature Range

-200 to +600 °C

Resolution

0.1°C

@ 25°C

±0.3% full scale

Accuracy

0-55°C

±0.5% full scale

Isolation

500V (backplane)

Conversion Time

40mS/ch

Backplane Power Consumed

100mA @ 5V

External Power Required

100mA @ 24V (+/-10%)

Terminal Type

Screw Type, Removable 15-posn

Optional Spring-clamp Plug

HE599TRM015

Storage Temp.

-25° to 70° Celsius

Operating Temp.

-0° to 55° Celsius

Relative Humidity

5 to 95% Non-condensing

Dimensions WxHxD

20mm x 90mm x 60mm

0.79” x 3.54” x 2.36”

Weight

63g (2.2 oz.)

CE & UL Compliance

CE, UL & C-UL

*requires a user defined function block for Cscape

(available for free download)


2

Wiring – I/O








3

Reported Data & Configuration Data


Data is reported to the OCS in signed integer format, with a single implied decimal place. For a
temperature of +457.4°C, with a data range configured for °C, the reported data value is 4574
decimal. For a temperature of -12.1°F, with a data range configured for °F, the reported data value
is -121 decimal.

The SmartRail RTD100 is configured using Cscape (9.1 or later). The following parameters are
configurable for the RTD100:

Cscape Configuration Data – Selectable per channel

Parameter

Selections

Enable

Channel Enable

Disable

American Std (α=0.00392)

Thermocouple Type

Japanese Std (α=0.003916)

°C

Data Range

°F


If you are using the common European (DIN) standard RTDs, configure the module for the American
Standard type. An extra calculation is then required in logic to convert the value reported by the
RTD100 into an accurate value. This calculation may be performed using a user defined function
block inserted into the Cscape logic program. This function block (DIN_RTD_FUN) is available for
download from the Horner APG web site. This function block performs the following calculation.

Y

=

4.70573965141697e-06

(x

2

)

+

1.01922059169856e+00

(x)

+

1.28999644570005e-02

where

Y = DIN temperature value and
x = American Standard temperature value



4

Installation / safety






a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, twisted pair wiring of the proper type should be used for best performance.
Maximum lead-wire resistance should be less than 10Ω.
c. Shields should be terminated at one end only, at the end providing the best noise shunting.

For detailed installation and a handy checklist that covers panel box layout requirements and
minimum clearances, refer to the hardware manual of the controller you are using.

When found on the product, the following symbols specify:




5

Technical Support

Technical Support at the following locations:

North America:
Tel: 317 916-4274
Fax: 317 639-4279
Web:

http://www.heapg.com

Email:

[email protected]

Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web:

http://www.horner-apg.com

Email:

[email protected]



RTD100 LED Status Indication

LED

Meaning
ON = Normal Operation
FLASH = I/O Error

RUN

OFF = No Power or I/O Error
ON = Normal Operation
FLASH = Open Circuit Detected

OK

OFF = No Readings

SmartRail

RTD Input Module (Pt-100)

HE599RTD100

0.1°C Resolution, typical

No part of this publication may be reproduced without the prior agreement and written
permission of Horner APG, Inc. Information in this document is subject to change without
notice.

Warning: Remove power from the OCS controller and any peripheral equipment connected
to this local system before adding or replacing this or any module.

Warning: Consult
user documentation.

Warning: Electrical
Shock Hazard.

+

-

24VDC

C

S

E

N.C.

C
H
4

C
H
3

C

S

E

C

S

E

C

S

E

C
H
2

C
H
1

+

_

24VDC @ 100mA
External Power

SHIELD GROUNDED
AT ONE END ONLY

E

S

C

E

S

C

E

S

C

E

S

C

Prefer Spring-clamps?

Optional Spring-clamp style plugs are
available as economical wiring accessories.
See specification table for part number(s).