Samlex America BW-01 User Manual

Battery monitor bw-01 | owner's manual, Description and features, Layout and dimensions installation

Advertising
background image

SAMLEX AMERICA, INC.

| 1

BATTERY MONITOR BW-01 |

OWNER'S MANuAl

Description and Features:

This unit is an Intelligent, microprocessor based,

panel mounted battery voltage monitor for display of the State of Charge of 12V / 24V

battery with the help of buzzer and different patterns of Red / Yellow / Green LEDs: steady

/ blinking / slow or fast “Walking LEDs”. 12V / 24V battery is detected automatically when

voltage of 7 to 32V is seen on connection of the battery. Following parameters / conditions

are displayed:

Terminal voltage

Charging in progress

Alarm at programmed low voltage threshold.

Alarm at programmed high voltage threshold

3- Day Timer / Switch OFF the unit for low voltage protection

layout and Dimensions

Installation:

Please refer to Figs 1 and 2 above. The unit consists of a 65 x 65 mm

front plate with 4 x 3.2 mm holes for flush mounting on a wall / panel with 4 screws (#4,

Tapping, Flat Head). The Printed Circuit Board (PCB) and Battery Input Connectors (0.25”/

6.3 mm Quick Connect Tabs) are located at the back of the plate and project out to a

depth of 25.5 mm. For flush mounting on the wall / panel, a pocket / slot measuring 30

mm x 30 mm x 40 to 50 mm depth is required to be made to accommodate the projection

at the back.
Use AWG # 22 to 26 wires (e.g. telephone wires) to connect to the battery (See

Fig. 2). Use a 0.5A fuse in series with the Positive wire. The fuse should be as close as

possible to the battery Positive terminal (preferably within 7”).
Refer to Fig 2. Battery Positive (+) and Negative (-) connections to the unit are made

through Battery Input Connectors “A” and “B” (1/4”/6.3 mm Male Quick Connect Tabs).

For this connection, use 0.25”/6.3 mm Female Quick Connect Receptacle Terminal Lugs on

the wire ends (See Fig 3).
12V / 24V battery is detected automatically when voltage of 7 to 32V is seen on

connection of the battery. At startup, Red LED is activated as a sign of power up. After

some time, the unit is initialized and 12V / 24V battery is recognized. The State of Charge

is displayed thereafter.

lED and Buzzer Indications for Voltage levels:

*NOTE: Term “Walking LEDs” has been used to indicate cyclical, sequential lighting

pattern of Red, Yellow and Green LEDs. This pattern indicates that charging is taking

place. Following 2 patterns are used:

“Walking lED’s - Fast” + Beep: Indicates charging at voltage that is higher than the

programmed value of High Voltage Threshold (14.8V (Preset) / 15.3V / 16V for 12V

battery and 29.6V (Preset) / 30.6V / 32.0V for 24V battery). The loop is: {Red » Yellow

» (Green + Beep) » All OFF}… repeats this sequential loop.

“Walking lED’s – Slow”: Indicates charging at voltage higher than 13.3V (12V

battery) / 26.6V (24V battery) but lower than the programmed value of High Voltage

Threshold (14.8V (Preset) / 15.3V / 16V for 12V battery and 29.6V (Preset) / 30.6V /

32.0V for 24V battery). The loop is: (Red » Yellow » Green»

All OFF)… repeats this sequential loop.

Status of lEDs

and Buzzer

Battery Voltage

indicated for 12V

Battery

Battery Voltage

indicated for

24V Battery

*Walking LED’s - Fast + Beep (Indicates

charging in progress and the voltage is

higher than the programmed threshold

of Over Voltage Alarm)

> 14.8 (Preset) /

15.3V / 16.0V

> 29.6V (Preset) /

30.6V / 32.0V

*Walking LED’s - Slow (Indicates

charging in progress under normal

conditions)

> 13.3 But <(14.8V

(Preset) / 15.3V /

16.0V)

> 26.6V But < (29.6V

(Preset) / 30.6V /

32.0V)

Green

> 12.4

> 25.0V

Green+Yellow

> 11.6

> 23.2V

Yellow

> 11.2

> 22.2V

Yellow+Red

> 10.9

> 21.8V

Red

> 10.5

>21.4V

(Green +Yellow + Red) - Blinking

-

> 21V

Following pattern indicates voltage is

below the programmed threshold for

Low Voltage Alarm:
(Red + Green) » (Yellow + Beep)…

repeats 10 times
» (Red + Green) » (Yellow)… repeats

10 times
» All LEDs OFF. Unit enters

Sleep Mode. There is a beep every min.

< 10.5 (Preset) or

< programmed

values of 10.6V

/ 10.7V / 10.8V

/ 10.9V / 11.0V

/11.1V / 11.2V

< 21V (Preset) or <

programmed values

of 21.2V / 21.5V

/ 21.6V / 21.8V

/ 22.0V / 22.2V /

22.4V

High Voltage Alarm during Charging:

Following voltage thresholds can be

programmed to warn about over voltage condition during charging (See programming

procedure given separately).

14.8V (Preset) / 15.3V / 16V for 12V battery

29.6V (Preset) / 30.6V / 32.0V for 24V battery

This facility can be used to indicate onset of “Equalization Stage” when charging Flooded

/ Wet Cell Batteries. During “Equalization Stage”, the battery is intentionally overcharged

to 15.3 to 16V (12V battery) / 30.6 to 32V (for 24V battery) for limited time of 1 to 3

Hrs. During this time, it is necessary to monitor the battery for overheating / electrolyte

level / measurement of individual cell voltages and for turning OFF Equalization at the

appropriate time.
The display pattern is “Walking LEDs – Fast” + Beep. In this pattern, the display / buzzer

loop is: {Red » Yellow » (Green + Beep) » All OFF}......Repeats this sequential loop.
NOTE: The unit will not reset even after the battery voltage drops below the programmed

Over Voltage Threshold. This is helpful to know that an over voltage condition existed. The

alarm can be reset manually as follows:

Press and hold Programming Button » Beep will be heard » Release the Button

low Voltage Alarm:

Following voltage thresholds can be programmed to warn

about low voltage condition (See programming procedure given separately).

14.8V (Preset) / 15.3V / 16V for 12V battery

29.6V (Preset) / 30.6V / 32.0V for 24V battery

When the programmed Low Voltage Threshold is reached, the following LED / Buzzer

pattern will be observed:
(Red + Green) » (Orange + Beep)…….Repeats 10 times
» (Red + Green) » (Orange)….. Repeats 10 times
» All LEDs OFF. Unit enters Sleep Mode. There is a beep every minute so that it is clear that

the unit is not in a “3 Day Off Mode.”
NOTE: The unit will reset only when the battery voltage rises to > 13.3V (for 12 V battery)

/ 26.6 V (for 24V battery) i.e. when charging takes place.

3-Day Timer:

A 3-Day Timer has been provided to automatically switch OFF the unit

after 3 days of switching ON of the Timer or if the battery voltage drops below 10.4V (for

12V battery) or 20.8V (for 24V battery). The Timer will be automatically switched OFF after

the battery voltage rises above 13,3V (for 12V battery) or 26.6V (for 24V battery).
ON / OFF Modes can be programmed as shown under heading “Programming

Alarm Thresholds / 3-Day Timer.”

3

2

1

4

5

3.2

56

65

56

65

Fig 1. BW-01 Front View

Fig 2. BW-01 Back View & Battery Connec-
tion (Note: Same dimensions as front view)

A

B

36

36

14.9

14.9

PCB

0.5A

Fuse

Wire AWG #22 to 26

Fig 2.:
A
– 1/4" (6.3mm) Quick Connect Tab Terminal

for connection to Positive (+) of the battery

B – 1/4" (6.3mm) Quick Connect Tab Terminal

for connection to Negative (-) of the battery

Fig 1.:
1
– Red LED
2 – Yellow LED
3 – Green LED
4 – Buzzer (at the back)
5 – Programming Button

Fig 3. 0.25”/6.3 mm Female Quick
Connect Receptacle Terminal Lug

Advertising