Configuring the inputs, Configuring system information, Configuring email notification – Chatsworth Products Remote Infrastructure Management (RIM-1000) User Manual

Page 2: Completing the installation

Advertising
background image

©2014 Chatsworth Products, Inc. All rights reserved. Chatsworth Products, CPI, CPI Passive Cooling, eConnect, MegaFrame, Saf-T-Grip, Seismic

Frame, SlimFrame, TeraFrame, GlobalFrame, Cube-iT Plus, Evolution, OnTrac, QuadraRack and Velocity are federally registered trademarks of Chats-

worth Products. Simply Efficient is a trademark of Chatsworth Products. All other trademarks belong to their respective companies. 7/14 MKT-60020-619

While every effort has been made to ensure

the accuracy of all information, CPI does not

accept liability for any errors or omissions

and reserves the right to change information

and descriptions of listed services and

products.

Configuring the Inputs

The eight non-isolated universal inputs are connected to TB2 and TB3.
Universal input channels can be individually configured through the RIM-
1000 to monitor a 4-20mA signal, a normally open (NO) dry contact relay or
a normally closed (NC) dry contact relay.

Making the Physical Connections

The following figure shows examples of input wiring.

Once you have wired the inputs, make note of the following:

Sensor type (analog or digital) connected to each channel.

For analog sensors, the high/low values.

For digital sensors, the non-alarm state - normally open (NO) or normally closed
(NC).

Configuring the Channels

Configure the input channels using the Inputs & Relays page of the RIM-1000 web
inteface. Click on the underlined label for the input you want to configure.

Configuring Inputs

A

Input can be Analog 4-20 mA or Digital NO or NC.

B

Applies only to analog inputs. Gain and offsett determine the correct

value for the RIM-1000.

C

Applies only to analog inputs. Hysteresis designates the amount an input

must change before returning to normal.

D

Applies only to analog inputs. Displays units on main menu, such as Deg F,

Deg C, %RH, Amps, Volts, psi, etc.

E

RIM-1000 current raw reading and calculated value.

F

Applies only to Analog inputs. High and Low alarm thresholds of range

being monitored.

G

This label is displayed on the RIM-1000 menu and the configuration menu.

H

Relay configuration link.

A

B

C

D

E

F

G

H

Configuring System Information

A

An alphanumeric name that you would recognize. This name appears on

the Main Menu and is included as part of email and pager notifications.

B

An integer greater than 5.

C

Consult your PDA manual for the correct width.

D

The number of points to be monitored. Maximum 104.

A

B

C

D

Configuring Email Notification

The RIM-1000 sends one email message per alarm instance to a maximum
of eight email recipients.

A

Refer to information from IT administrator.

B

Text that is easily recognized as notification from the RIM-1000.

C

Up to eight email recipients.

D

For ESMTP email authentication. Refer to information from IT

administrator.

A

B

C

D

Completing the Installation

Once you have completed the tasks in this quick start guide, the RIM-1000
can communicate over the network and monitor the inputs you configured.

Consult the RIM-1000 User Manual at

www.chatsworth.com/Products/Environmental-

Monitoring-and-Security/RIM-1000

for information about completing these additional

tasks:

System clock settings

Network time protocol settings

SNMP/Syslog settings

Modbus/Telnet settings

BACnet settings

User administration

URL links to IP-addressable devices

Nest/Egg configuration (for additional RIM-1000 appliances that will be
monitored by a central RIM-1000 appliance)

Trends

Alarm management

Common 4

Wire Sensors

Common 3

Wire Sensors

IE: CPI P/N

60111-001, 60111-002

Temperature Sensor

IE: CPI P/N

60111-004/60111-005

Temperature/

Humidity Sensor

IE: CPI P/N

60110-001

Power Fail

Monitor

IE: Common

Ground for

UPS

IE: CPI P/N 60109-001,

Spot Detector

4

5

6

7

Advertising