SDM-SIO1 Serial Input/Output Module

3.3 Examples for Connecting the SDM-SIO1 to Other

Equipment

3.3.1 RS-485 One to One Connection Example

1 C1

2 C2

3 C3

To

logger

4 G

5 +12V

6 G

100

R

or

higher

7

RX-A

R

8 CTS-B

9

RTS-Y

R

10 TX-Z

11 0V

RS-485

0V

12 Z

RS-485_B

13 Y

RS-485_A

14 B

RS-485_Z

15 A

RS-485_Y

RS-485
equipment with
termination
resistors

Notes:

• Z, Y, B and A are connected to their corresponding differential wire pairs
when in RS-485/RS-422 mode. Where A and Y are the ‘+’ lines and ‘B and Z
are the ‘-‘ lines.

• Connections 7-10 are connected internally to connections 12-15. This allows
for terminations resistors to be added when in RS-485 mode (if needed) or,
more than one connection to the I/O lines or TX and RX lines in RS-232 mode.

• If the use of termination resistors is required in RS-485 mode then they
should be connected between pins TX-Z and RTS-Y for the ZY line and CTS-
B and RX-A for the A B line (see diagrams elsewhere in document).

• In half duplex RS-485/RS-422 mode the Z Y and A B pairs are connected
internally by the hardware without the need for any user interaction. The user
should connect their wires to ZX and YS, as ‘A’ and ‘B’ are disabled.