Campbell Scientific SS100 Sensor Simulator User Manual

Page 6

Advertising
background image

SS100 Sensor Simulator

CRBasic Measurement Instruction:
VoltSe

(WindDir,1,mv2500C,1,1,0,_60Hz,360/2200,0)


Wind Speed (Use SS100 High Frequency Pulse Output)
Range:

0-50

m/s

Accuracy: +/- 5% > 5 m/s or 0.2 m/s < 5 m/s

Resolution: 0.1 m/s

Wind Speed Output: Linear, Calm = 3Hz, 50 m/s = 140 Hz


Wiring

SS100

CR1000

P P1
G


Multiplier and offset calculation:

Using the equation of a line with two known points (0,3) and (50,140):

y=mx + b; m = (50-0) / (140-3) = 0.365 m/s / Hz

b=y-mx; 50 - .365(140) = -1.095 m/s


CRBasic measurement instruction:

PulseCount (WS_ms,1,1 ,0,1,.365,-1.095) 'configured for high frequency

CR1000 Wind Speed and Wind Direction Example

'CR1000 Series Datalogger

'Declare Public Variables
Public WS_ms, WindDir

'Define Data Tables
DataTable (SS100,true,-1)
DataInterval

(0,60,Sec,10)

WindVector

(1,WS_ms,WindDir,FP2,False,0,0,0)

FieldNames

("WS_ms,WindDir,WindDir_SD1")

EndTable

'Main Program
BeginProg
Scan

(1,Sec,0,0)


'Analog Output - Simulated Wind Direction

VoltSe

(WindDir,1,mv2500C,1,1,0,_60Hz,360/2200,0)


'Pulse Output - Simulated Wind Speed

PulseCount

(WS_ms,1,1

,0,1,.365,-1.095)

'high frequency Hz


'Call

Output

Tables

CallTable

SS100


NextScan
EndProg

2

Advertising