Troubleshooting: piping details, Typical piping detail, Acorn controls – Acorn SFET VALVE User Manual

Page 5

Advertising
background image

Page 5 of 7

CAUSE

SOLUTION

PROBLEM

1. SET POINT DIFFICULT TO SET OR

CANNOT BE REACHED

SUPPLY TEMPS NOT WITHIN
SPECIFIED LIMITS

HOT AND COLD SUPPLIES ARE
REVERSED

CHECK DIFFERENTIAL TEMPERATURE
BETWEEN SUPPLIES AND OUTLET

REINSTALL VALVE WITH SUPPLIES
CONNECTED TO MARKED INLETS

2. DOES NOT MAINTAIN OUTLET

TEMPERATURE OR CHANGES

FLUCUATION IN SUPPLY
PRESSURES

CHECK VALVE/FILTERS BLOCKED
WITH DEBRIS

CHECK DIFFERENTIAL TEMPERATURE
BETWEEN SUPPLIES AND OUTLET

CLEAN CHECK VALVES/FILTERS

OVER TIME

3. DISCHARGE TEMPERATURE TOO

HOT OR TOO COLD

VALVE NOT ADJUSTED PROPERLY

READJUST VALVE TEMPERATURE PER
INSTALLATION INSTRUCTIONS

4. CROSS FLOW

CHECK VALVES FOULED

CLEAN CHECK VALVES/FILTERS

5 NO FLOW FROM VALVE

HOT AND COLD SUPPLY FAILURE
OR SHUTOFFS CLOSED

OPEN SHUTOFFS OR RESTORE HOT
AND COLD SUPPLIES

CHECK VALVE/FILTERS BLOCKED
WITH DEBRIS

CLEAN CHECK VALVES AND FILTERS

TYPICAL PIPING DETAIL

ET71 SERIES
VALVE

EMERGENCY

EYE/FACE WASH

SHOWN FOR

REFERENCE

HOT

WATER

SUPPLY

COLD

WATER

SUPPLY

TROUBLESHOOTING:

PIPING DETAILS:

Acorn Controls

Division of Acorn Engineering Company

®

, A member of Morris Group International

Date: 04/01/14

* In accordance with ASSE 1071

Valve Specifications:

Maximum Operating Pressure: ..................... 125 psi (861 kpa)

Maximum Hot Water Supply Temp: ..................... 180°F (82°C)

Outlet Temp. Range: ................................... 60-95°F (15-35°C)

Minimum Hot Water Supply ........................................ 5°F (3°C)
Above Set Point
Flow Rate at 45 psi (310 kpa) differential:
ET71-1: ............................................................ 12 gpm (45 lpm)
ET71-2: .......................................................... 43 gpm (163 lpm)
ET71-3: .......................................................... 86 gpm (326 lpm)
ET71-4: ........................................................ 150 gpm (568 lpm)

Minimum Flow*:
ET71-1 ........................................................... 1.5 gpm (5.7 lpm)
ET71-2 .............................................................. 1 gpm (3.8 lpm)
ET71-3 .............................................................. 2 gpm (7.6 lpm)
ET71-4 ............................................................ 3 gpm (11.4 lpm)

Bypass Flow Rate Minimum*:
ET71-1: ........................................................ 6.5 gpm (24.5 lpm)
ET71-2: .......................................................... 25 gpm (95 lpm)
ET71-3: .......................................................... 60 gpm (227lpm)
ET71-4: .......................................................... 80 gpm (303 lpm)

Cold Water Failure Maximum*:
ET71-1: .......................................................... 0.5 gpm (1.9 lpm)
ET71-2: ............................................................ 1 gpm (3.8 lpm)
ET71-3: ............................................................ 1 gpm (3.8 lpm)
ET71-4: ............................................................. 1 gpm (3.8 lpm)

SFET Installation & Operation Manual

Manual #7802-119-000