8

Installation

Ventilation

DIRECT FLUE ARRANGEMENT
When the installation of a mechanically driven exhaust

hood is impractical the oven may be vented by a direct

flue arrangement.

WARNING!!

It is essential that the direct flue be installed

as follows. Incorrect installation will result in

unsatisfactory baking and oven damage.

The flue must be class B or better with a diameter of 10”

(25.4 cm). The height of the flue should rise 6-8 ft (2-2.5

m) above the roof of the building or any proximate struc-

ture. Never direct vent the oven into a hood. The flue

should be capped with a UL Listed type vent cap to isolate

the unit from external environmental conditions.
The direct vent cannot replace air consumed and vented

by the oven. Provisions must be made to supply the room

with sufficient make-up air. Total make-up air require-

ments for each oven section should be approximately 30

CFM per section. To increase the supply air entering the

room, a ventilation expert should be consulted.
Installing the draft hood
Ovens ordered for direct venting are supplied with a draft

hood. Install the draft hood as follows:
1. Place the draft hood over the flue connector.
2. Secure both ends with the sheet metal screws pro-

vided.

Draft Hood

Flue

Front of Oven

Figure 6

VENTING PROBLEMS
Blodgett gas deck ovens use the natural principal of heat

rising as the basic method of ventilation. If the venting of

any deck oven is either restricted or forced in any way

the baking characteristics of the oven will be adversely

affected.
Examples of forced venting include:
• installation of a fan in a direct vent pipe
• use of a canopy type hood without the draft diverter
Examples of restricted venting include:
• use of tees and elbows
• long horizontal runs
Insufficient make-up air can cause heated air and com-

bustibles to remain in the oven shortening the life of the

components.