AMX Dual Zero Cross Module RDM-2ZC User Manual

Installation sheet

Advertising
background image

Installation Sheet

RDM-2ZC Dual Zero Cross Module

2400 W

The RDM-2ZC Dual Zero Cross Module is a dual 2400 W zero-cross relay
built for long term, reliable switching of electronic fluorescent ballasts, elec-
tronic transformers and incandescent lamps. It is designed for use with the
RDA series of enclosures, in an AMX Lighting™ modular digital dimming
system. The module's 120, 240, and 277 VAC ratings are CE, UL, and C-
UL approved.

RDM-2ZC UL and C-UL Ratings

120-277 VAC, 2400 W

240/277 VAC, 2400 W

Suggested Switched Loads

Incandescent

Electronic transformers

HID ballast

Electronic and magnetic ballast

Specifications

Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)

Non-phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 7 in-lbs. (0.8 N/M)

Max. wire size: 10 AWG (4 mm²)

Wire stripping length: 0.28" (7 mm)

Weight: 2.0 lbs. (0.91 kg)

BTU/hr: 300

Control current: 45 mA per relay (90 mA total) @ 12 VDC

Caution: Pre-Installation Notes

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times.

Test loads for shorts before connecting.

Use low voltage wires with a 300 volt rating or greater.

Use field installed copper conductors.

All electrical ratings are for continuous duty.

For indoor use only.

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-2ZC to the AMX Lighting Master

Lighting Application Drawing

FIG. 1 RDM-2ZC

Low-voltage control
wiring: 4-pin connector
to AMX Lighting master
controller

Zero cross relay A

Zero cross relay B

Line in (hot)

Load out

High-voltage
connections

Mounting
points

FIG. 2 RDM-2ZC connections

FIG. 3 RDM-2ZC wiring configuration

Pin 4 (GND)

Pin 3 (RLY)
Pin 2 (DIM)

Pin 1 (+12 V)

3 (-)

1 (+)

RDM-2ZC 4-pin module connector

4-pin plug from RDM series module

NOTE: The 4-pin plugs from the module connector to
the 4-pin connector on the master (black plug cover facing up).

Ballast

Circuit breaker
panel

Neon lights

(cold-cathode, on/off)

Neutral

Load

All neutrals are common
to the Neutral block in the
enclosure. Provide a
separate neutral for
each load.

(B) Load

(B) Line in (HOT)

Load

Neutral

Fluorescent Ballast

(A) Line in (HOT)

(A) Load

Safety ground

Advertising