Vili. circulating air and filters – Amana VR8205 User Manual

Page 18

Advertising
background image

18

HEAT ANTICIPATOR SETTING
Adjust the heat anticipator in the room to obtain the proper
number of heating cycles per hour. The heat anticipator is
a wire-wound adjustable heater that prevents the room
temperature from “overshooting” the room thermostat set-
ting. The heat anticipator must be set at 0.7 amps. The heat
anticipator is part of the thermostat. If the thermostat fails
for any reason, replace the thermostat.

LINE VOLTAGE CONNECTION FOR OPTIONAL
HUMIDIFIER AND ELECTRONIC AIR CLEANER
The control module is equipped with line voltage accessory
terminals used for controlling the power to an optional field-
supplied humidifier and/or electronic air cleaner.

Accessory Load Specification

Air Cleaner: 1.0 Amp max. at 120 VAC
Humidifier: 1.0 Amp max. at 120 VAC

Accessory Installation:

Follow the electronic air cleaner and humidifier manufactur-
ers’ instructions for mounting and electrically grounding
these accessories. Check that the power supply to the
furnace has been disconnected. Wire the accessories to
the control module as shown below. All connections to the
control module are to be made through 1/4 inch female
terminals.

If it is necessary to supply additional line voltage wiring to
the interior of the furnace, the wiring must comply with all
local codes. This wiring must have a minimum temperature
rating of 105°C and must be routed away from the burner
compartment. All line voltage wire splices must be made
inside the furnace junction box.

Control Module

C

ool

H

eat

Pa

rk

Pa

rk

Li

ne

T

ran

sf

o

rme

r

EAC

Hu

m

Ci

r

Li

ne

T

ran

sf

o

rme

r

EAC

Hu

m

Hot 120 VAC

Neutral

120 VAC

Air

Cleaner

Humidifier

Optional
Accessories

{

Figure 24

Line Voltage Connection for Accessories

Accessory Operation: The furnace control module ener-
gizes the humidifier whenever the induced draft blower is
energized (when an air cleaner is installed on the system,
the humidifier is not energized until the air cleaner is
energized). The control module energizes the air cleaner
whenever the air circulation blower is energized.

VIlI. Circulating Air and Filters

DUCTWORK - AIR FLOW
Duct systems and register sizes must be properly designed
for the CFM and external static pressure rating of the
furnace. Ductwork should be designed in accordance with
the recommended methods of “Air Conditioning Contrac-
tors of America” Manual D.

A duct system must be installed in accordance with Stan-
dards of the National Board of Fire Underwriters for the
Installation of Air Conditioning, Warm Air Heating and
Ventilating Systems. Pamphlets No. 90A and 90B.

A closed return duct system must be used, with the return
duct connected to the furnace. Supply and return con-
nections to the furnace may be made with flexible joints to
reduce noise transmission. To prevent the blower from
interfering with combustion air or draft when a central return
is used, a connecting duct must be installed between the
unit and the utility room wall. A room, closet, or alcove must
not be used as a return air chamber.

When the furnace is used in connection with a cooling unit,
the furnace should be installed in parallel with or on the
upstream side of the cooling unit to avoid condensation in
the heating element. With a parallel flow arrangement, the
dampers or other means used to control the flow of air must
be adequate to prevent chilled air from entering the furnace
and, if manually operated, must be equipped with means to
prevent operation of either unit unless the damper is in the
full heat or cool position.

When the furnace is installed without a cooling coil, it is
recommended that a removable access panel be provided
in the outlet air duct. This opening shall be accessible when
the furnace is installed and shall be of such a size that the
heat exchanger can be viewed for visual light inspection or
such that a sampling probe can be inserted into the air-
stream. The access panel must be made to prevent air
leaks when the furnace is in operation.

When the furnace is heating, the temperature of the return
air entering the furnace must be between 55°F and 100°F.

When a furnace is installed so that supply ducts carry air
circulated by furnace to areas outside the space containing
the furnace, the return air shall also be handled by a duct
sealed to the furnace casing and terminating outside the
space containing the furnace.

Filters - Read This Section Before Installing The Return
Air Ductwork

Filters must be used with this furnace. Discuss filter main-
tenance with the building owner. Filters do not ship with this
furnace, but must be provided by the installer. Filter(s) must
comply with UL900 or CAN/ULCS111 standards. If the
furnace is installed without filters, the warranty will be
voided.

The following chart shows recommended minimum filter
sizes for each furnace model. Larger sizes are also accept-
able.

Advertising