MAINTENANCE (continued)

Rinsing and Replacing the TAC Cartridge

(VZN-441H-T5 ONLY)

1. Turn off the water supply to the system and turn off the

water to all downstream equipment.

2. Press the

FLUSH button to initiate the flush cycle.

Repeat several times to ensure the permeate tank is

empty.

3. Press and hold the Red Pressure Relief Button on the

top of the TAC Housing (Figure 11) to lower the water

level inside the housing by 2 to 3 inches.

4. Remove the TAC Housing (Figure 10).
5. Empty any water into a drain and discard the old TAC

Cartridge (Figure 11).

6. Inspect the O-ring on the TAC Housing. Replace the

O-ring if it is cracked, twisted, or missing.

7. Lubricate the O-ring with an approved food grade

lubricant and install into the TAC Housing.

8. Install the new TAC Cartridge into the TAC Housing.
NOTE: Make sure the End Seal gaskets are in place in

the recessed grooves on both ends of the TAC Cartridge

(Figure 12).
9. Screw the TAC Housing (containing the TAC Cartridge)

into place on the TAC Head. The Housing will come

to a hard stop at the end of the thread. Use a Filter

Wrench if necessary.

10. Direct the water from the Rinse Ball Valve to a drain.
NOTE: It is important to direct the system outlet to drain

as the water resulting from the flush should NOT be used.
11. Slowly turn on the water to the system and allow water

to flow through the TAC Cartridge and Housing to clear

out trapped air and any carbon fines that may be pres-

ent.

12. To help remove trapped air from the TAC Housing,

press the Red Pressure Relief button on the top of the

Housing until water just begins to come out.

13. Rinse the TAC Cartridge for at least 5 minutes.
NOTE: Do NOT consume the water used for rinsing the

TAC Cartridge.
14. When the TAC Cartridge rinsing is complete, close the

Rinse Ball Valve and turn on the water to all down-

stream equipment.

15. Reconnect the water to service. The system is now

ready for use.

System Sanitization

The system and downstream plumbing should be sanitized

every six months. When necessary, follow the procedure in

Sanitizing the System and Lines in the Installation section

of this manual.

O-ring

TAC

Housing

TAC

Cartridge

TAC

Head

Red Pressure

Relief Button

Gasket

TAC

Housing

TAC

Cartridge

Figure 10. Removing the TAC Housing (VZN-441H-T5 only)

Figure 11. Replacing the TAC Cartridge (VZN-441H-T5 only)