A.J. Antunes & Co TTC 8051420110 User Manual

Ttc installation information, Specifications

Advertising
background image

1-630-784-1000 Fax: 630-784-1651

Page 1 of 4

P/N 1011091 06/10

1-800-253-2991

A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188

Dimensions

Panel Cutout

Mounting Bracket and Screw

Bracket and Screw Positions

IMPORTANT

Please read these instructions carefully to assure

correct installation. This equipment must be

installed by a licensed electrician. Prior to being

put into operation, check all wiring and function of

the unit.

TTC Installation Information

Specifications

Sensor Type: Thermocouple (Type J or K)
NOTE: Ungrounded thermocouples are required when

multiple controllers/indicators are used or if the transform-

er is grounded.
Accuracy: 1% Full Scale ± LSD
Power: 12 VAC/DC (24 VAC, 115 VAC, 230 VAC with

external transformer), 50/60 Hz.
Control: On/Off
Output: 10 Amp. Relay, Standard (Resistive Load) or

12-16 VDC @ 30 mA
Temperature Range: 50º to 990ºF (10ºC to 530ºC)
Ambient Operating Temperature: -30ºF to 140ºF

(-35ºF to 60ºC)

Ambient Storage Temperature: -40ºF to 180ºF

(-40ºF to 82ºC)

Connections: Terminal - Screw Terminal
Hysteresis: Typically 1-2° unless offered otherwise
Display: 3-Digit LED (0.56” Ht.)
Package: Panel Mount Epoxy Encapsulated
Shipping Weight: 1 lbs. (.45 kg)

2.8”

(71 mm)

.308”

(8 mm)

3.10”

(79 mm)

3.10”

(79 mm)

1.4”

(36 mm)

1.4”

(36 mm)

NOTE: Dimensions are for reference only.

2.82”

1.13”

Advertising
This manual is related to the following products: