A.J. Antunes & Co DF 8563140061 User Manual

Df installation information, Dimensions installation, Specifications

Advertising
background image

A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188

Dimensions

Installation

IMPORTANT

Please read these instructions carefully to assure

correct installation. This equipment must be

installed by a licensed electrician. Prior to being

put into operation, check all wiring and function of

the unit.

DF Installation Information

Specifications

Sensor Type: 10K thermistor probe, 10- or 20-foot

lengths with bolt-down eyelet sensor.
Input Power: 24 VAC, 50/60 Hz. or 115 VAC, 50/60 Hz.
Adjustable Digital Inputs: Time: 1-10 minutes in 1 min.

steps - Temperature: 30ºF–75ºF in 5º increments.
Outputs: Output drive for Freezestat relay K2 and

associated LED2. Relay is normally de-energized—if

the preset temperature is not reached within the preset

time the relay will latch (energized) thereby opening the

normally closed contact and turning off the externally

controlled device. Only removing and reapplying power

will reset the circuit and start the time period over again.
Relay: S.P.D.T., 8 amps, dry contact output,

1/4” spade terminal connection.
Shipping Weight: 1 lb. (.45 kg) without cover

2 lbs. (.9 kg) with cover

Operation

Output drive for Freezestat relay K2 and associated LED2.

Using an appropriate tool, set the Freezestat to the

proper temperature and time intervals. Attach thermistor,

(available in 10 or 20 foot lengths with bolt down

eyelet sensor). To avoid electrical shock or damage

to equipment, disconnect power before installing or

servicing.
Under normal operating conditions the relay is normally

de-energized, if the preset temperature is not reached

within the preset time, the relay will latch (energized)

thereby opening the normally closed contact and turning

off the externally controlled device.
Only removing and reapplying power will reset the circuit

and start the time period over again.

1-630-784-1000 Fax: 630-784-1651

Page 1 of 2

P/N 1011094 06/10

1-800-253-2991

To Thermistor

Indicates
Fault
Condition

120V/24V

Temperature

Settings

Timer

Settings

3.5”

88.9 mm

3.5”

88.9 mm

NOTE: Dimensions are for reference only.

Advertising
This manual is related to the following products: