Versa Plus Air Pressure Switches

Versa Plus Air pressure switches by Antunes Controls

monitor positive, vacuum, or differential air pressures.

The integrated contacts make or break the circuit to the

desired set point. The large adjustment knob provides

set point indication and aids in ease of adjustment. The

Versa Plus Air series can be factory adjusted for applica-

tions that require other differential settings.

Dimensions

IMPORTANT

Please read these instructions carefully to assure

correct installation. This equipment must be

installed only by a licensed electrician who is

experienced with combustion safeguard control

systems and understands the functions of inter-

locking switches, such as gas pressure switches.

Prior to being put into operation in conjunction

with the combustion safeguard systems, all

switches should be tested for proper range setting

and proper wiring. Check piping connections and

switch house for leaks with a soap bubble test. All

exhaust fans and blowers should be inspected and

checked for proper rotation prior to starting up.

Versa Plus Air Pressure Switches Installation Information

Specifications

Electrical Ratings: 6A @ 120 VAC, 6A @ 240 VAC,

1/8 HP, 120 & 240 VAC. Integrated S.P.D.T. contacts.
Adjustable Operating Pressure: 0.2 to 50 mbar

(different

ranges)

Max. Surge Pressure: 7 PSI (482 mbar)
Pressure Connections: 1/8” NPT positive & vacuum

ports; 1/4” hose barb OD.
Ambient Operating Temperature: 5°F to 180°F

(-15°C to 82°C)

Field wiring to be rated @ 90°C (194°F) for maximum

ambient
Shipping Weight: 0.5 lbs. (.227 kg)
Options:

Mounting brackets can be oriented in any of the 90°

positions.

Vacuum

Inlet

1/2” Conduit

Knockout

Pressure

Inlet

3"

(76 mm)

3"

(76 mm)

2 5/16"

(59 mm)

Vacuum

Inlet

1/2” Conduit

Knockout

Pressure

Inlet

3"

(76 mm)

3"

(76 mm)

2 5/16"

(59 mm)

Model

Part No.

W.C.

mbar

NPT Switches (activate on pressure fall/vertical mount)

FAN 1.2

8281001001

.08"–.5"

0.2–1.2

FAN 010

8281002010

.5"–4"

1.2–10

NPT Switches (activate on pressure rise/horizontal mount)

FAN 050

8281003050

1"–20"

2.5–50

Hose Barb Switches (activate on pressure fall/vertical mount)

FAB 1.2

8291001001

.08"–.5"

0.2–1.2

FAB 010

8291002010

.5"–4"

1.2–10

Hose Barb Switches (activate on pressure rise/horizontal mount)

FAB 050

8291003050

1"–20"

2.5–50

Installation

All switches are tested at the factory in a vertical position.

Mounting diaphragm in vertical position is the preferred

method.

Air Connection

Tubing recommended as minimums: 1/4” copper or alumi-

num tubing, or 1/8” pipe.

All tubing and pipe must be clean and free from oil, dirt,

and chips. If piping runs over five feet long, use larger

size tubing or pipe and reduce size at switch connection.

Ranges Available

Note: Dimensions are for reference only.

Advertising