HID EDGE EVO EWM-M Wiegand Module Installation Guide User Manual

Edge evo, Specifications, Door & reader module

Advertising
background image

The EDGE EVO Door and Reader module is designed for interfacing with the EDGE EVO Hi-O Networked Controller to electronic door

components and a traditional Wiegand reader.
Designed for providing interface to traditional discrete access inputs and outputs, the Door component provides four analog/digital inputs

and two outputs. Configure the Door component in two ways; as a primary door interface to REX, Door Position Switch, Battery Fail, Power

Fail, Lock, and Aux (Group 1) or as a general purpose input/output module (Group 2).
Configure the Reader Module in two ways, either a Group 1 or Group 2 device. When two readers are present at one access control point,

the secure reader side is assigned Group 1.

Specifications

Door Module

CONDITIONS

VOLTAGE DC

(VDC)

CURRENT

(Amp)

POWER

(W)

OPERATING

TEMPERTURE CABLE LENGTH

UL REF

NUMBER

Input

DC Input (NSC)

+12 VDC

0.04 Amp

0.48

32° - 122°F
(0° - 50° C)

Inputs

= 500 ft (150 m)

Outputs

= 500 ft (150 m)

Hi-O CAN Bus Total Length 100 ft (30 m) -

22 AWG ● 0.65mm ● 0.33mm

2

Maximum between drops 30 ft (10 m)

22 AWG ● 0.65mm ● 0.33mm

2

MEDMAxNN

x = K for Black

G for Grey

+24 VDC

0.04 Amp

0.96

DC Input (MAX)

+12 VDC

0.80 Amp

9.6

+24 VDC

0.80 Amp

19.2

Supervised inputs
(AC, Batt, REX, Door Mon) (MAX)

0-5 VDC
Reference

0.005 Amp
(Sink)

0.025

Output

Strike *** /
AUX
NC or NO
DC Output
(MAX)

AUX 12 VDC
Input @
Controller

Unregulated (Wet)
Jumpers

+10 to +12 VDC 0.70 Amp*

8.40

AUX 24VDC
Input @
Controller

Unregulated (Wet)
Jumpers

+23 to +24 VDC 0.70 Amp*

16.80

Regulated (Wet)
Jumpers – 12 VDC

+10 to +12 VDC 0.70 Amp*

8.40

PoE Input @
Controller

Unregulated (Wet)
Jumpers

+16.5 to 24 VDC 0.30 Amp*

7.2

Regulated (Wet)
Jumpers – 12 VDC

+10 to +12 VDC 0.50 Amp*

6.0

AUX 12-24 VDC
/ PoE Input @
Controller

Jumpers Set to Dry

+12 to 24 VDC
External

2.00 Amp**

24.00

Reader Module

CONDITIONS

VOLTAGE DC (VDC) CURRENT

(Amp)

POWER

(W)

OPERATING

TEMPERTURE CABLE LENGTH

UL REF

NUMBER

Input

DC Input (NSC)

+12 VDC

0.03 Amp

0.36

32° - 122°F
(0° - 50° C)

Wiegand

= 500 ft (152.4 m) - 22 AWG ● 0.65mm ● 0.33mm

2

MEWMAxNN

x = K for Black

G for Grey

+24 VDC

0.72

DC Input (MAX)

+12 VDC

0.70 Amp

8.4

+24 VDC

16.8

Data 1/CLK , Data 0/Data (MAX) 0-5 VDC Reference

N/A

N/A

Output

Reader PWR
Output VDC
(MAX)

AUX 12 VDC
@ Controller

+9.8 to +12.25 VDC

0.30 Amp*

3.67

AUX 24 VDC
@ Controller

0.60 Amp*

7.35

PoE Input @
Controller

0.50 Amp*

6.12

GRN LED, RED LED,
Beep and Hold (MAX)

0-5 VDC Reference

0.005 Amp
(sink)

0.025

External Tamper - (MAX)

+5 VDC (NOM)

0.017Amp

0.085

NSC = Normal Standby Condition

** Each Relay

* Combined output rating not to exceed V*I = W

*** Shared between relays

1.2 Amp (+24VDC AUX Input, 28.8 W)

1.2 Amp (+12VDC AUX Input, 12.96 W)

EDGE EVO

®

Door & Reader Module

EDWM-M

I

nstallatIon

G

uIde

82363-901, Rev C.1

December 2012

© 2009 - 2012 HID Global Corporation. All rights reserved.

15370 Barranca Parkway

Irvine, CA 92618-2215

USA

Advertising