On power, True on line sinewave double conversion ups, Technical features – Atlantis Land A03-OP6000 User Manual

Page 2

Advertising
background image

A

TLANTIS

L

AND

S.p.A. - Viale De Gasperi 122 - 20017 Mazzo di Rho - Milano - ITALY

Phone: +39 - (0)2 - 93.90.60.85 Fax: +39 - (0)2 - 93.90.61.61 - Web: www.atlantis-land.com - E-Mail: [email protected]

Subject to change without notice

True On Line Sinewave
Double Conversion UPS

A0

3-

OP

60

00

_S

E_

06

3

TECHNICAL FEATURES

MODEL

A03-OP6000

Power Rating

6000 VA - 4200 W

INPUT

Voltage (Vac)

160-280

Frequency (Hz)

50 ± 5% (Auto Sensing)

Phase

SingleLine+Neutral+Ground

Input Power Factor

> 0.99 (Full Load)

OUTPUT

Voltage (Vac)

220/230/240

Voltage Regulation

± 2%

Voltage Adjustement

± 0%; ± 1%; ± 2%; ± 3%

Frequency Stability

±0.2% (Free Running)

Frequency Regulation

± 1%; ± 3%

Wave Form

Sine Wave, THD<4%
(no load to full load)

Rated Power Factor

0.7

Transfer Time

0 ms

Crest Factor

3:1

Efficiency (AC to AC)

>90% (Normal)

Efficiency

(AC to AC, ECO)

>98% (ECO)

Run Time (Full Load)

> 8 min

DC Start

Yes

BATTERY

Type

Maintenance Free Sealed

Lead Acid

Quantity (pcs)

20

Voltage (Vdc)

240

Recharge Time

4 Hours to 90%

Supplem. Charger

Optional 1000W Isolated

chargers

PROTECTION

Short Circuit

Hold Whole System

OverHeat

Switch to Bypass

High Voltage Trip

Switch to Backup Mode

Battery Low

Alarm and Switch Off

Noise Suppression

Complies with EN50091-2

Spike Suppression

Complies with EN610000-4-5

OverLoad

AC Mode:
1) <105% continuously Alarm
2) 105%-150% delay 40
seconds before switching to bypass
4) >150% immediately
switching to bypass
Backup Mode: Same Delay
Time as AC Mode, then
completely shutdown

MODEL

A03-OP6000

ALARMS

Audible and Visual

Line Failure, Battery Low, Tranfer to Bypass,
System Fault Conditions

DISPLAY

Self Diagnostics

Push Button (On Demand)

LED+LCD

Utility, Battery, Inverter, Bypass, Self-Test,

OverLoad, Load/Battery Level and Fault

PHYSICAL

Dim (WxDxH)

290 x 645 x 748 mm

Outlets

Terminal Block

Net Weights (Kgs)

80

ENVIRONMENTAL

Operating

Temperature

0-40

o

C

Temperature Warning

The battery design life is based on a
temperature of 25

o

°C. Ambient temperature

above this range will reduce battery life

Altitude / Humidity

0-2000m up to 40°C, 3000m up to 35°C /
90% RH Humidity max (non-condensing)

Noise

< 45 dB (at 1 metere)

COMPUTER
INTERFACE

Interface Type

Standard RS232 Interface / SNMP

Protocol

MEGATEC Protocol

AS 400 Interface

Optional As400/ Basic Photo Contact
Interface Board provides Utility Failure,
Battery Low, Bypass Active, UPS
Shutdown functions

SNMP Adaptability

Slot for Standard SNMP Card

Compatibility of

Bundled Software

UPSilon2000 for: Novell NetWare,
Windows95/98, Windows NT, Windows ME,
Windows 2000 and XP, Linux and FREE BSD

Optional Software

UPSilion for UNIX, SNMP Adapter, USBMate

SAFETY
CONFORMANCE

Quality Assurance

ISO9001 Certified Company

Marks

CE