Mounting bracket locations – American Aldes RDF 8-8IP User Manual

Page 6

Advertising
background image

BRADENTON, FL 34203
P:

941.351.3441

F:

941.351.3442

E: [email protected]

operation. The entire motor and fan
assembly is mounted on a drop-down
hinged access panel for service and
inspection, and can be removed from
the fan without disassembly of the
ducting connections.

Controls: The fans can be operated
manually, or automatically by a
programmable timer or dehumidistat
and may also be operated in
conjunction with a variable speed
control.

Locating and Installing the Fan:
The compact dimensions and
versatile mounting options permit
installation above drop ceilings,
between ceiling joists, or within a
small soffi t location. The fan can
be installed either horizontally or
vertically.

Airflow Balancing: The flow
rates are automatically set with
preset ALDES Constant Airflow
Regulators.

A passively controlled element in
each duct run infl ates or defl ates
automatically in response to system
pressure to maintain constant
airfl ow.

02/09

www.americanaldes.com

AIRFLOW

CFM

3" INTAKE DUCT TO FAN

Recommended

Max. Duct Length from

Grille to Fan (ft.)

SMOOTH

FLEXIBLE

10

225

180

20

65

50

30

30

25

40**

20

15

50**

10

10

*This table should only be used as a general guide. Actual duct length allowances may be longer on some models. Contact the factory for
assistance. **CAR Flow Regulators not available over 35 cfm. NOTE: If longer duct runs are required than permitted in the table above, use smooth
ducting and/or increase the diameter.

ELECTRICAL DATA

MPVS 100 / 120

120 V, 60 Hz., .19/.29 amp.,

22/38 W Max., 2980 / 3135 RPM

Above ratings are intended for sizing

electrical wring only. Actual consumption

will be lower.

TOTAL

EXHAUST

RATE CFM

FAN DISCHARGE DUCT

Assumes low pressure drop

vent cap

FOR EACH

ELBOW

DEDUCT

4" SMOOTH

4" FLEXIBLE

60

40 ft

20 ft

3" Diameter

= 3 Feet

75

25 ft

15 ft

90

18 ft

12 ft

100

15 ft

9 ft

120

11 ft

8 ft

135

8 ft

6 ft

MOUNTING BRACKET

LOCATIONS