System checks, Thermostat installation, Warning – Atwood Mobile Products HYDRO FLAME 2540 User Manual

Page 4: Diagnostic chart, Propane gas pressure test, Static pressure test

Advertising
background image

4

THERMOSTAT INSTALLATION (

MODEL

2H2C

)

FURNACE

-

MODEL

2540

MUST USE THIS THERMOSTAT

The thermostat is very sensitive.

HANDLE WITH CARE AT ALL TIMES

.

Locate thermostat 48˝ to 54˝ above floor on an

INTERIOR

wall. Pick a dry

area where air circulation is good.

EXTERIOR

wall location must have a

3/4˝ spacer between thermostat and exterior wall.
1. Be sure all electrical power has been disconnected from the air con-

ditioner, furnace and the power supply.

2. Do not install the thermostat where there are unusual heating condi-

tions: such as direct sunlight, heat producing appliances (television,
radio, wall lamp, etc.) or a furnace or air conditioner supply register.

3.

ATTACHING THE WALL THERMOSTAT

. Separate the thermostat body from the

sub-base by gently squeezing the top and bottom. Pull wires through
access hole in base plate. Attach thermostat sub-base to the wall at
the desired mounting location. Mount the sub-base to the wall before
connecting the wires. See instruction provided with thermostat.

SYSTEM CHECKS

ƽ

WARNING

FIRE OR EXPLOSION

Never check for leaks with an open flame.

DIAGNOSTIC CHART

A diagnostic LED is located inside the exterior access cover on the out-
side edge of the horizontal (2) stage control board. The following
graph defines the codes.

NUMBER OF LED FLASHES

DIANOSTIC INFORMATION

LOCKOUT

1

Low Input voltage

SOFT

2

Ignition Failure

SOFT

3

Open High Limit

SOFT

4

Stuck Sail Switch

HARD

5

Module Fault

HARD

NOTE

: A

SOFT

lockout is a condition that is timed and will make addition-

al attempts to correct the problem. A

HARD

lockout requires reset

of the thermostat or turning the power switch off then back on.

PROPANE GAS PRESSURE TEST

The furnace and any individual shut-off valve must be disconnected
from gas supply piping system during any pressure testing of system
at test pressures of more than 1/2 PSI.

Before furnace is connected piping systems must be tested to be leak
free. The test must maintain air pressure of at least 6˝ of mercury or 3
PSI for at least 10 minutes.

The entire piping system must be maintained within a range of 10-14˝
W.C. when all appliances are in operation. Test gas connections for
leakage with a leak test solution.

STATIC PRESSURE TEST

CASING STATIC PRESSURE TABLE

If duct static pressure cannot be set, casing static pressure should not exceed
the values listed below when taken cold.

DUCTING SYSTEM

OPERATING VOLTS

FLEXIBLE

HARD

DC

MODELS

12

0.25˝ W.C.

0.35˝ W.C.

Voltage greater than indicated will cause higher static readings.
Reducing the number of duct turns and stretching ducts will increase
air flow and reduce static pressure. Adding ducts or increasing dis-
charge system (hard ducting) will also reduce static pressure. NOTE:
Special tool required to take casing static pressures.

Location for Static Pressure Tap for casing is on the back of casing
(top left corner) (

FIG

3).

VALVE

MOTOR

IGNITION

CONTROL

SAIL

SWITCH

+12 VDC

-12 VDC

YELLOW

LIMIT
SWITCH

BULK HEAD
CONNECTOR

DUAL
CONTROL

WHITE

YELLOW

YELLOW

BLUE

ORANGE

BROWN

BLACK

BLACK

BLUE

RED

RED

HIGH TENSION

CHASSIS
GROUND

CHASSIS
GROUND

ELECTRODE

RED

RED

WHITE

GREEN

+THERMO

-THERMO

ELECTRONIC
DIGITAL
THERMOSTAT

1

1

1

2

2

2

3

3

3

4

4

4

5

5

5

6 6

6

CUSTOMER SUPPLIED WIRE

IMPORTANT: If any original wire has to
be replaced, it must be replaced with
type 105˚C or it's equivalent.

2-STAGE - MODEL 2540

WIRING

4