Typical wiring connections, Electrical access, Figure 6 – Allied Air Enterprises (2 User Manual

Page 5: Figure 5

Advertising
background image

506252-01

Page 5 of 13

Issue 0902

Power supply to the unit must comply with all applicable codes
and the National Electical Code (NEC) or Canadian Electrical
Code (CEC). A fused disconnect switch should be field provided
for the unit. The switch must be separate from all other circuits.

If any of the wire supplied with the unit must be replaced,
replacement wire must be of the type shown on the wiring
diagram. Electrical wiring must be sized to carry minimum
circuit ampacity marked on the unit. Use copper conductors
only.
Each unit must be wired with a separate branch circuit
and be properly fused.

Thermostat
The room thermostat should be located on an inside wall
where it will not be subject to drafts, sun exposure, or heat
from electrical fixtures or appliances. Follow the
manufacturer’s instructions enclosed with thermostat for
general installation procedure. Color-coded insulated wires
(#18 AWG) should be used to connect thermostat to unit.

Four wires are required for cooling.

Unit must be grounded in accordance with
national and local codes. Failure to ground unit
properly can result in personal injury or death.

WARNING

Figure 6

Typical Wiring Connections

R

R

C

C

C

C

R

R

L2

L1

Y

Y

Y1

Y

L1

L2

L3

POWER WIRING

208/230-1-60

(75°C MIN. WIRE)

POWER WIRING

24V CONTROL WIRING

(NEC CLASS 2)

TYPICAL WIRING CONNECTION

1 PHASE

GROUND
SCREW

THERMOSTAT

OUTDOOR UNIT

THERMOSTAT

OUTDOOR UNIT

GROUND
SCREW

POWER WIRING

200/230-3-60, 460/575-3-60

(75°C MIN. WIRE)

24V CONTROL WIRING

(NEC CLASS 2)

POWER WIRING

TYPICAL WIRING CONNECTION

3 PHASE

* W1, W2 CAN BE USED TO STAGE ELECTRIC

HEAT ACCESSORY ON

MODELS.

15 & 20 KW

* 5 & 10 KW HEATER ACCESSORY FUNCTION

W1 ONLY.

OFF

* W1, W2 CAN BE USED TO STAGE ELECTRIC

HEAT ACCESSORY ON 15 & 20 KW MODELS.

* 10 KW HEATER ACCESSORY FUNCTION OFF

W1 ONLY.

ECONOMIZER

NOT

INSTALLED

ECONOMIZER

W1

W

W

W1

G

G

G

G

W2

Y2

W2

BLUE

YELLOW

YELLOW

GREEN

BLACK

Do not connect connections except when

required by the indoor thermostat. Refer to the

thermostat installation instructions.

C

CAUTION

Do not connect connections except when

required by the indoor thermostat. Refer to the

thermostat installation instructions.

C

CAUTION

Figure 5

Electrical Access

Heater Power Entry

Thermostat

Entry

Line Voltage

Entry