Characteristics, 3) recording the heating programs, 4) recording the econo programs – Aube Technologies TH102D User Manual

Page 3: 1) proportional and on/off controls, 2) characteristics

Advertising
background image

720-102002-A 3/4

3) Recording the heating programs

Select the AUTO mode.

Press on PGM button once.

The default values or the last recording of

program 1 will be displayed.

The default values are :

• 20 °C and the time -- -- : -- --

The days Monday to Friday are displayed to

show that this program is for weekdays.

Press on HOUR and MIN buttons until 6:30 AM

is displayed.

Press on or until 20 °C is displayed.

The first program is recorded.

Press on PGM button again to record or modify

weekday programs 2, 3 and 4 and weekend

programs 1, 2, 3 and 4.

Use HOUR, MIN, or buttons to modify

the time and setpoint of programs.

Programming is now completed. Press on RET

button or wait for the "automatic return" to exit

the programming mode.

Note: A program time left at -- -- : -- -- is con-

sidered inactive.

To reset a program, use PGM button to select

the program, then press on MODE button.

To review programs, press on PGM button

successively to see the programs one after the

other and make modification if required.

4) Recording the ECONO programs

Select the ECONO mode.

Press on PGM button once.

The default values or the last recording of pro-

gram 1 will be displayed.

The default values are :

• 10 °C and the time -- -- : -- --

Use DAY, HOUR, MIN and or buttons to

record the day, the time and the setpoint of

program 1.

Press a second time on PGM key.

The default values or the last recording of pro-

gram 2 will be displayed.

Use DAY, HOUR, MIN and or buttons to

modify the day, time and setpoint of program 2.

Programming is now completed. Press on RET

button or wait for the "automatic return" to exit

the programming mode.

CHARACTERISTICS

1) Proportional and on/off controls

This thermostat works differently than the conventional electro-mechanic one.

The latter can have a differential of temperature up to 4 °C while this electronic

thermostat has one of only 0.3 °C. This slight oscillation eliminates the discomfort

often found with conventional electro-mechanic thermostats.

The proportional controller determines the amount of power required by the

electric heating system to maintain the exact ambient temperature of the

temperature setting.

To see this process, the display shows, in

real time, the percentage of power applied

to the electric heating system.

If you have programmed the heating con-

trol to ON/OFF to control a fan equipped

system, the display will show the fan indi-

cator and 100% when the heating system

will turn ON and 0% when it will turn OFF.

In this case, the temperature regulation

will be ±0.5 °C around the setpoint.

2) Characteristics

• Model: TH102D

• Electronic programmable line voltage thermostat (2 wires non polarized)

• Supply: 120/240 VAC, 50/60 Hertz

• Load: 10.4 A maximum, 1.0 A minimum (Resistive only)

• Power: 2500 W @ 240 VAC or 1250 W @ 120 VAC

• Power consumption (off): 860 mW

• Approvals: CSA / UL

• Display range: 0 to 99 °C (0 to 99 °F)

• Setting range: 5 to 27 °C (40 to 80 °F)

• Storage: -20 to 50 °C (-4 to 120 °F)

• Temperature regulation: 0.3 °C (proportional), +/- 0.5 °C (ON/OFF)

• Precision: ± 0.5 °C (2500 W) of temperature setting

• 10 programs: 4 weekday programs, 4 weekend programs and 2 ECONO

programs

NOTE :

In normal use at full capacity (2500 W), the housing temperature

of the thermostat can reach 35 to 40 °C.

Advertising