Installation and operation manual – Panasonic S25FM3HPQ User Manual

Page 3

Advertising
background image

S-20~125FM3HPQ
Urban Multi air conditioner
4PW15114-1A

Installation and operation manual

1

C

ONTENTS

Page

Before installation .............................................................................. 1

Selecting installation site ................................................................... 2

Preparations before installation ......................................................... 2

Indoor unit installation........................................................................ 3

Refrigerant piping work...................................................................... 3

Drain piping work............................................................................... 4

Electric wiring work............................................................................ 5

Wiring example and how to set the remote controller........................ 6

Wiring example .................................................................................. 6

Installation of the decoration panel.................................................... 7

Test operation .................................................................................... 7

Maintenance ...................................................................................... 8

Wiring diagram ................................................................................ 10

B

EFORE

INSTALLATION

Leave the unit inside its packaging until you reach the
installation site. Where unpacking is unavoidable, use a sling of
soft material or protective plates together with a rope when
lifting, this to avoid damage or scratches to the unit.

Refer to the installation manual of the outdoor unit for items not
described in this manual.

Caution concerning refrigerant series R-410A:
The connectable outdoor units must be designed exclusively for
R-410A.

Do not place objects in direct proximity of the outdoor unit and
do not let leaves and other debris accumulate around the unit.
Leaves are a hotbed for small animals which can enter the unit.
Once in the unit, such animals can cause malfunctions, smoke
or fire when making contact with electrical parts.

Precautions

Do not install or operate the unit in rooms mentioned below.
-

Places with mineral oil, or filled with oil vapour or spray like in
kitchens. (Plastic parts may deteriorate.)

-

Where corrosive gas like sulphurous gas exists. (Copper
tubing and brazed spots may corrode.)

-

Where volatile flammable gas like thinner or gasoline is used.

-

Where machines generating electromagnetic waves exist.
(Control system may malfunction.)

-

Where the air contains high levels of salt such as air near the
ocean and where voltage fluctuates a lot (e.g. in factories).
Also in vehicles or vessels.

When selecting the installation site, use the supplied paper
pattern for installation.

Do not install accessories on the casing directly. Drilling holes in
the casing may damage electrical wires and consequently cause
fire.

Accessories

Check if the following accessories are included with your unit.

Screws for fixing panels are attached to the air inlet panel.

Optional accessories

There are two types of remote controllers: wired and wireless.
Select a remote controller according to customer request and
install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.

When installing bottom suction: air inlet panel and canvas
connection for the air inlet panel.

S-20FM3HPQ

S-40FM3HPQ

S-80FM3HPQ

S-25FM3HPQ

S-50FM3HPQ

S-100FM3HPQ

S-32FM3HPQ

S-63FM3HPQ

S-125FM3HPQ

Urban Multi air conditioner

Installation and

operation manual

READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY PANASONIC WHICH
ARE SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR PANASONIC DEALER FOR
ADVICE AND INFORMATION.

Metal clamp

1 piece

Paper pattern for

installation

1 piece

Drain hose

1 piece

Insulation for fitting

1 each

Washer for

hanging bracket

8 pieces

for gas pipe

for liquid pipe

Screws for duct flanges

1 set

S-20•25•32FM3HPQ

6 pieces

Screws for fixing

the paper pattern

for installation

6 pieces

S-40•50FM3HPQ

8 pieces

S-63FM3HPQ

12 pieces

S-80•100•125FM3HPQ

16 pieces

Other: installation and operation manual, fuse

Advertising
This manual is related to the following products: