Aube Technologies Electric Heating Solid-State Relay RT850 User Manual

Rt850, Installation instructions, Application

Advertising
background image

RT850

400-274-000-D 2007-12-21 1/2

The RT850 Solid State Relay is designed to control a line-voltage
resistive load from a 24 VAC control signal or from signal sources of
4 to 32 VDC. It can be used with fast-commuting thermostat (e.g.
cycles of 15 seconds).

The RT850 is compatible with both mechanical and 2-wire or 3-wire
electronic thermostats (with or without batteries).

I

The RT850 must be mounted on a 4” x 4” electrical box.

WARNING:

The relay must be mounted so the heat sink fins are ver-

tical or facing upwards. You should also provide space above the
heat sink for warm air to escape. Disregarding this warning may
result in improper operation of the relay. Refer to the diagram below
for correct mounting guidelines.



All wiring must comply with national and local electrical
code regulations.



The installation should be carried out by an electrician.



Disconnect power before the installation to prevent electri-
cal shock.

n

Perform the wiring as per figures 1 and 2.

o

Secure the relay to the electrical box.

p

Apply power to the heating system.

q

Verify the installation by increasing the setpoint temperature at
the thermostat to activate the relay (the LED on the relay should
light up).

WARNING:

In the following wiring diagrams, the relay is illustrated

sideways for the purpose of showing the terminal wiring. Refer to
installation section for proper positioning of the relay.

Figure 1:

Connection to a 2-wire low voltage thermostat using a
24-VAC control signal

Figure 2:

Connection to a 3-wire low voltage thermostat using a
24-VAC control signal

n

Application

1.

o

Installation

2.

p

Typical Wiring Diagrams

3.

You must provide an overload protection and disconnect
as required.

External 24-VAC

transformer

Low-voltage

2-wire

thermostat

4 x 4 electrical box

Load

Black

Red

You must provide an overload protection and disconnect
as required.

External 24-VAC

transformer

Low-voltage

3-wire

thermostat

4 x 4 electrical box

Load

Black

Red

RT850

Installation Instructions

Electric Heating Solid-State Relay

400-274-000-D (RT850) ENG.fm Page 1 Friday, December 21, 2007 2:15 PM

Advertising