OPEN POSITION SWITCH (BOTTOM)

OPTIONAL MOTOR RREAK

TERMINALS 6-12 ARE USED FOR OPTIONAL LIMIT SWITCHES OR HEATER & THERMOSTAT

OPTIONAL 15 WATT 115 VAC HEATER & THERMOSTAT

LINE VOLTAGE

W1

W2

F1 OPTIONAL

24 VAC 60 HZ 1 PH

RED

BLUE

5 AMP

115 VAC 60 HZ 1 PH

RED

BLUE

1 AMP

230 VAC 60 HZ 1 PH

YELLOW

BLUE

.75 AMP

DUE TO HIGH AC INDUCTION FEEDBACK VOLTAGE THROUGH THE CAPACITOR AND
TERMINALS 3 & 4, MULTIPLE ACTUATORS CANNOT BE WIRED IN PARALLEL. SEPARATE
RELAYS (ISOLATED CONTACTS) MUST BE PROVIDED FOR EACH ACTUATOR. DEVICES
CONNECTED TO TERMINALS 3 & 4 MUST BE RATED FOR 250 VAC OR (440 VAC FOR 230 VAC
OPERATION VOLTAGE).