Technical device information – Panasonic LA16MI User Manual

Page 4

Advertising
background image

4

TECHNICAL DEVICE INFORMATION

1

Type and order code

LA12MI

LA16MI

2

Design

2.1

Degree of protection according to EN 60 529 for a compact unit or heating

element

IP 24

IP 24

2.2

Installation location

Outdoors

Outdoors

3

Performance Data

3.1

Operating temperature limits:
Heating water fl ow / return fl ow

°C

Max. 55 / min. 25 Max. 55 / min. 25

Air

°C

-20 to+35

-20 to+35

3.2

Heating water temperature difference at

standard rating condition

K

5

5

Heat output / COP

at A7 / W35

1

kW / ---

12.0 / 4.67

16.0 / 4.23

at A2 / W35

1

kW / ---

11.0 / 3.50

14.0 / 3.10

at A-7 / W35

1

kW / ---

12.0 / 2.90

14.1 / 2.72

3.3

Sound power level

2

dB(A)

62

64

3.4

Heating water fl ow rate

m³/h

2.1

2.8

3.5

Air fl ow

m³/h

4800

5400

3.6

Refrigerant; total fi lling weight

Type / kg

R410A / 2.3

R410A / 2.3

3.7

Lubricant; total fi lling quantity

Type / Litre

FV50S (PVE) / 1.2 FV50S (PVE) / 1.2

4

Dimensions, connections and weight

4.1

Device dimensions without connections

H x W x L mm 1410

Ч 1283 Ч 320 1410 Ч 1283 Ч 320

4.2

Device connections to heating system

Inch

1 1/4” ext. thread 1 1/4” ext. thread

4.3

Weight of the transportable unit(s) incl. packaging

kg

165

165

5

Electrical Connection (Heat Pump)

5.1

Nominal voltage; fuse protection

V / A

230 / 32

230 / 32

5.2

Norminal power consumption

1

A7 W35

kW

2.57

3.78

5.3

Starting current (Inverter driven) A7 W35

A

Gradual increase

from 0-12

Gradual increase

from 0-18

5.4

Nominal current A7 W35 / cos

ϕ

A / ---

11.6 / 0.96

17.1 / 0.96

5.5

Power input of integral fan and pump

3

W

60 / 180

60 / 180

6

Electrical Connection (Back-Up Heater)

6.1

Nominal voltage; Frequency; Fuse protection

V / Hz / A

230 / 50 / 26

230 / 50 / 26

6.2

Norminal power consumption

kW

6.0

6.0

7

Heating Water Circuit

7.1

Expansion Vessel

Litre / Bar

10 / 3

10 / 3

7.2

Pressure Relief Valve

Bar

Open 3.0 /

Close 2.65

Open 3.0 /

Close 2.65

7.3

Free pressure, heating circulating pump (max speed)

kPa

83

83

8

Other design characteristics

8.1

Defrosting

Automatic

Automatic

Type of defrosting

Reverse Cycle

Reverse Cycle

8.2

Heating water in device protected against freezing

yes

yes

8.3

Controller internal / external

External

External

1)

These data characterise the size and performance of the system according to EN 14511 with clean heat exchangers. Abbreviations have the
following meaning, e.g. A2 / W35: outside temperature 2°C and heating water supply temperature 35°C. A2 / W35 test, takes into account
defrosting as per EN 14511.

2)

According to EN 12102, EN ISO 3744.

3)

Power input to pump relates to factory setting, speed 2. Fan is variable speed, rated input relates to maximum input power.

Advertising